39
Settings Parameters
GB
Model 9010/9020 SIL
WARNING!
Setting a wrong region may result different functionality of the control unit in relation with regional
standards.
"A" (ALARM) SETTINGS - OUTPUT WITH RELAY
P21
Decimal Places
Defines a number of decimal places for gas concentration displayed
Full scale range
Max.decimal places
Default setting
1000 - 9000
0
0
100 - 999
1
0
10 - 99
2
1
1- 9
2
2
P27
Region
CHS
Settings for region China (complies with CCCF standards)
EU
Settings for Europe and International region (complies with ATEX
standards if ATEX mode is activated)
USA
Settings for North America region (complies with CSA standards)
Region setting sets the unit in compliance with different regions requirements.
Only EU and International version is a subject of description in this manual. For detailed settings
for other regions (China, USA) please refer to individual manuals for these regions