Model 9010/9020 SIL
12.5 4-20 mA Transmitter Connections
Control Units 9010 SIL and 9020 SIL can accept, respectively, one or two input signals originating
from transmitters. These transmitters, with a 4-20 mA circuit will have to have the right CE (EU)
type certificate and will have to conform to Section 1.5 of Attachment II of Directive 2014/34/EU.
Control unit channels A and B configured for an input signal of 4-20 mA
Measurement range 0-100 % LEL
Fig. 19 Response curve for mA input (Equal for both Channel A and Channel B)
Input4/20 mA
Theoretical reading
Display reading 9010/9020 SIL Module
Ch A
Ch B
2
-12,5
-d1
-d1
4
0
0
0
6
12,5
12
12
8
25
25
25
10
37,5
37
37
12
50
50
50
14
62,5
62
62
16
75
75
75
18
87,5
87
87
20
100
100
100
21
106,3
EEEE
EEEE
22
112,5
EEEE
EEEE
Input signal
(mA)
C / W/ A
Horn
Failure
2
in normal state
in normal state
activated
4-20
depends on alarm setting activated with a new alarm activated with a new failure
21
activated
activated
activated
22
activated
activated
activated
Содержание 9010 SIL