![MSA 9010 SIL Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/msa/9010-sil/9010-sil_operating-manual_1846295066.webp)
65
Appendix
GB
Model 9010/9020 SIL
12.6 Detectors Connection Data Sheet
Detectors Connection Data Sheet Series 47K- PRP (S47K- ST) Gas Detector
WARNING!
Before connecting the measuring head reduce detector current to minimum
The cable screen is connected to the control unit only.
Detector type:
Catalytic/passive/constant current supply (3 wire passive)
Detector simulation module:
Order No. 10030263
For further details see detector's operation manual.
Bridge current
310 mA
Maximum nominal current
350 mA
Power consumption
1.0 W typical (without cable length)
Cable type
3 core, 80 % screened
Maximum loop resistance
36 ohms
Maximum cable length
1000 m (at wires cross section 1.5 mm
2
)
Wires allowed
Screw terminals: cross section 0,5 -2,5 mm
2
Spring terminal: cross section 0,5 -1,5 mm
2
Cable diameter
7 ….12 mm
Junction box II 2G Ex d IIC T6 or T4
II 2D Ex tD A21 IP6x T85 °C or T135 °C
Order No. 10051080
Junction box II 2G Ex e IIC T6 or T4
II 2D Ex tD A21 IP6x T85 °C or T135 °C
Order No. 10051091
Mounting
Wall mounted
Содержание 9010 SIL