Gas Pipe Sizing Tables
Pipe Size
Length (including fittings)
10 ft
(3 m)
20 ft
(6 m)
3/4 in
360
247
199
170
151
137
126
117
110
104
92
1 in
678
466
374
320
284
257
237
220
207
195
173
1-1/4 in 1,390
957
768
657
583
528
486
452
424
400
355
1-1/2 in 2,090
1,430
1,150
985
873
791
728
677
635
600
532
2 in
4,020
2,760
2,220
1,900
1,680
1,520
1,400
1,300
1,220
1,160
1,020
2-1/2 in 6,400
4,400
3,530
3,020
2,680
2,430
2,230
2,080
1,950
1,840
1,630
3 in
11,300
7,780
6,250
5,350
4,740
4,290
3,950
3,670
3,450
3,260
2,890
4 in
23,100 15,900 12,700 10,900
9,660
8,760
8,050
7,490
7,030
6,640
5,890
30 ft
(9 m)
40 ft
(12 m)
50 ft
(15 m)
60 ft
(18 m)
70 ft
(21 m)
80 ft
(24 m)
90 ft
(27 m)
100 ft
(30 m)
125 ft
(38 m)
454
312
250
214
190
172
158
147
138
131
116
949
652
524
448
397
360
331
308
289
273
242
1,790
1,230
986
844
748
678
624
580
544
514
456
3,670
2,520
2,030
1,730
1,540
1,390
1,280
1,190
1,120
1,060
936
5,500
3,780
3,030
2,600
2,300
2,090
1,920
1,790
1,670
1,580
1,400
10,600
7,280
5,840
5,000
4,430
4,020
3,690
3,440
3,230
3,050
2,700
16,900 11,600
9,310
7,970
7,060
6,400
5,890
5,480
5,140
4,860
4,300
29,800 20,500 16,500
14,100 12,500
11,300
10,400
9,690
9,090
8,580
7,610
60,800 41,800 33,600
28,700 25,500
23,100
21,200
19,800
18,500
17,500
15,500
1/2 in
3/4 in
1 in
1-1/4 in
1-1/2 in
2 in
2-1/2 in
3 in
4 in
Pipe Size
Length (including fittings)
10 ft
(3 m)
20 ft
(6 m)
30 ft
(9 m)
40 ft
(12 m)
50 ft
(15 m)
60 ft
(18 m)
70 ft
(21 m)
80 ft
(24 m)
90 ft
(27 m)
100 ft
(30 m)
125 ft
(38 m)
In Cubic Feet (ft
3
) per hour (0.60 Specific Gravity; 0.5 in WC Pressure Drop). Contact your gas supplier for
BTU/ft
3
ratings. Use 1,000 BTU/ft
3
for simplified calculations. This table is recommended for supply pressures
less than 6 in WC.
In Cubic Feet (ft
3
) per hour (0.60 Specific Gravity; 3.0 in WC Pressure Drop). Contact your gas supplier for
BTU/ft
3
ratings. Use 1,000 BTU/ft
3
for simplified calculations. This table is recommended for supply pressures
less than 6 in WC.
Maximum Natural Gas Delivery Capacity
NOTE: The tables below are for reference only. Please consult the gas pipe
manufacturer for actual pipe capacities. The tables below are referenced from the
2012 National Fuel Gas Code.