Troubleshooting
54
Nothing appears on
the display control
panel, but the water
heater is operating.
This occurs when
communications are
lost from the control
to the display.
Check for loose
connections and proper
pin
alignment/engagement
on the control’s
connector.
Correct wiring per wiring
diagram, including the
connection of the
transformer to the control.
Power the water heater
off and on using the
power button on the
display board and check
for operation.
Replace the display module.
Display
Condition
Diagnostic
Possible Corrective
Actions