4 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
37
5993419/02 EN
VACUTAP
®
VMS
®
7. Ensure that the transformer's circuit breaker cannot be closed.
ð
Passive protection test
8. Activate the sensor on the snap-action switch.
ð
Sensor is in the OPERATION position.
9. Leave the transformer's danger zone.
10. Close the transformer's circuit breaker with isolating switches open and
the transformer grounded on all sides.
11. Activate the sensor on the snap-action switch.
ð
Sensor is in the OFF position.
12. Ensure that the transformer's circuit breaker is open.
ð
Active protection test.
13. Activate the sensor on the snap-action switch to reset the pressure moni-
toring device.
ð
Sensor is in the OPERATION position.
14. Secure the cover cap.
4.1.6 Commissioning the transformer
ü
The signaling contact for falling below the minimum insulating fluid fill level
in the on-load tap-changer's oil conservator is looped into the tripping cir-
cuit of the circuit breaker.
ü
The protective relay and additional protective devices are looped into the
circuit breaker's tripping circuit.
ü
The motor-drive unit and all protective devices are functioning correctly
and are ready for use.
ü
The oil compartment of the on-load tap-changer is completely filled with
insulation fluid.
ü
All stop-cocks between on-load tap-changer and oil conservator of the on-
load tap-changer are open.
1. Switch on transformer.
2.
NOTICE!
Inrush current impulses can be significantly greater than the
transformer rated current and may lead to current paths with asymmetrical
or non-sinusoidal curve shapes and, as a result, overload the on-load tap-
changer during the diverter switch operation. Only perform tap-change op-
erations - whether under no load or under load conditions - once the in-
rush current impulse has subsided.
Содержание VACUTAP VMS
Страница 1: ...On load tap changer VACUTAP VMS Operating Instructions 5993419 02 EN Selector size C ...
Страница 69: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 69 5993419 02 EN VACUTAP VMS 9 2 Selector ...
Страница 71: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 71 5993419 02 EN VACUTAP VMS 9 3 On load tap changer head ...
Страница 74: ......
Страница 75: ......
Страница 76: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 76 5993419 02 EN VACUTAP VMS 9 4 Tools 9 5 Additional drawings ...
Страница 79: ......