Accuracy
+/- 1 k
Z < 20 k
L
+/- 5 % *
Z
L
>= 20 k
Alarm Value
1 k to 1 M
Factory Alarm Value
50 k
120 k
DC Circuits
AC Circuits
Fixed Hysteresis
+5%
AC and DC circuits
Standard Response Time (per circuit) T
R
1.1 s
Typical
Actual Response Time (per circuit) T
R
(Assumes static impedance to earth)
(750,000 x C ) + 0.3
E
seconds
Product Response Time
T
R
X Number of Circuits in Operation
Typical
System Leakage Capacitance (C
E
)
(per circuit)
0.1 F
100 F
Min.
Max.
Factory Set Max. Leakage Capacitance (C
E
)
1 F
per circuit
*See section 2.5 for an explanation of measurement accuracy with regard to the insulation resistance of DC monitored circuits.
*Accuracy de-rated to -5% to +6% in the presence of strong radiated EM fields at 20 V/m at 800 MHz to 1 GHz and 10 V/m at 1.4 GHz
to 2 GHz.
A typical mobile digital telecommunications device must be placed within 20 mm of the SA380-IT enclosure to experience these
levels.
Measuring Circuit
Measuring Voltage
+/- 46 V
Measuring Current
< 700 A
Internal Resistance & Impedance
> 45 k
no resistive cable fitted
System Resistance & Impedance
> 70 k
resistive cable fitted
Measuring Circuit is only connected to a
single Monitored Circuit at any one time
Internal System Check Frequency
Every 30 s
Earth Loop Circuit
Measuring Voltage
+/- 3.5 V
Max.
Measuring Current
< 500 A
System Resistance & Impedance
> 25 k
FE to SE
Tolerance to Stray Interference Voltage
+/- 500 mV pk.
Max.
Measurement Range
0 to 2 k
Accuracy
+/- 0.5
R
E
< 10
+/- 5 %
R
E
>= 10
Alarm Value
0 to 2 k
Factory Alarm Value
1 k
Fixed Hysteresis
+5%
Output Ports
Содержание SA380-IT
Страница 41: ...Select Internet Protocol Version 4 TCP IPv4 then click Properties Use the following IP settings then click OK...
Страница 43: ...Open the App...
Страница 44: ...If your IP is 192 168 100 115 the the web based configuration and diagnostics tool will load automatically...
Страница 50: ...The SA380 IT will not perform any measurements if the time is not set...
Страница 60: ......