6
APN
The name of the GSM access point the
SA380-IT is to connect to. It is set-up by
the SIM provider.
7
APN Username
Many GSM Access Points require
username and password authentication to
allow connection. Change these here.
8
APN Password
Many GSM Access Points require
username and password authentication to
allow connection. Change these here.
9
Earth Loop AoC %
Sets the "Acquire-on-Change" threshold for
reporting "earth loop resistance" change to
the EAMS (see section 4.10)
10
Earth Loop Alert Level
If the earth loop resistance exceeds this
level, the SA380-IT will report a hardware
fault and stop measurement of monitored
circuits.
11
AC Leakage Alert Level
If the resistance to earth of any AC
monitored circuit falls below this level, the
SA380-IT will report a earth fault.
12
DC Leakage Alert Level
If the resistance to earth of any DC
monitored circuit falls below this level, the
SA380-IT will report a earth fault.
13
Circuit Settling Time (ms)
This parameter governs the maximum
allowable time to measure the voltage and
resistance to earth of a individual
monitored circuit.
Ensure that the level is
appropriate for your
organisations needs and
complies with any legal safety
obligations.
Ensure that the level is
appropriate for your
organisations needs and
complies with any legal safety
obligations.
It is up to the user to specify an
appropriate time-out value,
based upon the trade-off
between desired accuracy and
speed of measurement.
The equation for calculating
measurement time per circuit
is: (750,000 x C ) + 0.3 seconds.
E
Where C is the maximum
E
expected capacitance to earth of
the monitored circuit. The
factory default is set at C = 1 F.
E
Содержание SA380-IT
Страница 41: ...Select Internet Protocol Version 4 TCP IPv4 then click Properties Use the following IP settings then click OK...
Страница 43: ...Open the App...
Страница 44: ...If your IP is 192 168 100 115 the the web based configuration and diagnostics tool will load automatically...
Страница 50: ...The SA380 IT will not perform any measurements if the time is not set...
Страница 60: ......