No.
Name
Description
1
Back
Navigates back to the live measurements
screen and terminates
.
technicians mode
2
Circuit Name & Connection Status
The name of the monitored circuit. A green
dot indicates a live connection to the
device. A red dot denotes that the
connection has been lost.
The physical input of the device to which
this monitored circuit is connected is shown
below.
3
Dump
Displays a detailed diagnostic data dump
(for manufacturers use).
4
Time
The current time.
5
Voltage
The monitored circuits present voltage. Not
displayed if earth loop resistance has been
selected.
6
Resistance
AC monitored circuits show equivalent
resistance to earth (R
L
).
DC monitored circuits show equivalent
resistance to earth of each circuit leg (R a
B
nd R ).
N
The Earth Loop circuit shows the present
resistance between FE and Loop Earth
terminals.
Technicians Mode
Whilst in technicians mode, only the
selected circuit is measured. This improves
response time for the circuit of interest to
aid faulting activities.
No other monitored circuit is measured,
earth loop resistance is not measured
(unless selected), device integrity checks
are not performed.
If the user should forget to leave
technicians mode,
will
normal mode
automatically resume after a period of 4
hours.
Green Text
..is used to denote monitored circuits where
resistance to earth is
the defined
above
alert thresholds.
..is used to denote that earth loop
resistance is
the defined alert
below
threshold.
Orange Text
..is used to denote that the monitored
circuit is suffering from a recoverable
device interlock.
The user should manually exit
technicians mode when it is no
longer required such that
other measurements
recommence.
Содержание SA380-IT
Страница 41: ...Select Internet Protocol Version 4 TCP IPv4 then click Properties Use the following IP settings then click OK...
Страница 43: ...Open the App...
Страница 44: ...If your IP is 192 168 100 115 the the web based configuration and diagnostics tool will load automatically...
Страница 50: ...The SA380 IT will not perform any measurements if the time is not set...
Страница 60: ......