3.1) Overview
Before commencing installation please consider the following:
The SA380-IT back panel is reproduced below showing the connector layout:
It is wise to conduct a
on the monitored circuits both prior to, and after installation, but
energising
manual insulation test
before
the SA380-IT. This will help verify correct installation of the measurement circuit wiring.
A
between Functional Earth and Loop Earth connections after installation, but
energising SA380-IT
manual continuity test
before
will help verify correct installation of the earth-loop circuit wiring.
Check all fuses / links are
at the system termination point for each monitored circuit and the SA380-IT power supply prior
removed
to installation. Test all wiring
re-inserting any fuses / links.
before
Only one insulation monitoring device may be used on a single interconnected circuit. Installation of additional monitoring devices
will cause each device to "fight" the other, resulting in incorrect readings on both devices.