![Motovario EM16-123 F-20 Series Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/motovario/em16-123-f-20-series/em16-123-f-20-series_manual_1839482037.webp)
37
Group 09- Communication function setup
No.
Description
Range
Factory
Setting
Unit
Note
09-00
Assigned Communication
Station Number
1 ~ 32
1
-
*2*3
09-01
RTU/ASCII Code Selection
0: RTU Code
1: ASCII Code
0
-
*2*3
09-02
Baud Rate Setting (bps)
0: 4800
1: 9600
2: 19200
3: 38400
2
bps
*2*3
09-03
Stop Bit Selection
0: 1 Stop Bit
1: 2 Stop Bits
0
-
*2*3
09-04
Parity Selection
0: Without Parity
1: With Even Parity
2: With Odd Parity
0
-
*2*3
09-05
Data Format Selection
0: 8-Bits Data
1: 7-Bits Data
0
-
*2*3
09-06
Communication Time-Out
Detection Time
0.0 ~ 25.5
0.0
Sec
09-07
Communication Time Out
Operation Selection
0: Deceleration to Stop
(00-15: Deceleration Time 1)
1: Coast to Stop
2: Deceleration to Stop
(00-17: Deceleration Time 2)
3: Continue Operating
0
-
09-08
Comm. Fault Tolerance Count.
1 ~ 20
3
09-09
Wait Time of Inverter
Transmission
5 ~ 65
5
ms
Group 10- PID Function Setup
No.
Description
Range
Factory
Setting
Unit
Note
10-00
PID Target Value Selection
(When 00-05\00-06=6 This
Function is Enabled)
0: Potentiometer on Keypad
1: Analog Signal Input. (AI1)
2: Analog Signal Input. (AI2)
3: Frequency Set by Communication
4: Keypad Frequency Parameter
10-02
1
-
*1
10-01
PID Feedback Value Selection
0: Potentiometer on Keypad
1: Analog Signal Input. (AI1)
2: Analog Signal Input. (AI2)
3: Frequency Set by Communication
2
-
*1
10-02
PID Target(Keypad Input)
0.0~100.0
50.0
%
*1
10-03
PID Mode Selection
0: Disabled
1: Deviation D Control.
FWD Characteristic.
2: Feedback D Control
FWD Characteristic.
3: Deviation D Control
Reverse Characteristic.
4: Feedback D Control
Reverse Characteristic.
0
-