Group 07- Start/Stop Command Setup
No.
Description
Range
Factory
Setting
Unit
Note
07-04
Direct Running on
Power Up
0: Enable Direct run on power up
1: Disable Direct run on power up
1
-
07-05
Delay-ON Timer
1.0~300.0
1.0
Sec
07-06
DC Injection Brake Start
Frequency
0.10 ~ 10.00
1.5
Hz
07-07
DC Injection Brake
Level (Current Mode)
0.0 ~ 150.0
50.0
%
07-08
DC Injection Brake
Time
0.0 ~ 25.5
0.5
Sec
07-09
Stopping Method
0: Deceleration to stop
1: Coast to stop
0
-
07-10
Starting Methods
0: Normal Start
1: Speed Search
0
-
07-11
Starting method for auto
restart after fault
0: Speed Search
1: Normal start
0
-
07-12
Power Loss Ride
Through Time
0.0 ~ 2.0
0.5
Sec
07-13
Main Circuit Low
Voltage Detection Level
150.0~210.0 300.0~420.0
190.0/3
80.0
Vac
07-14
Kinetic Energy Back-up
Deceleration Time
0.0~25.0: KEB Deceleration Time
0.0
Sec
07-15
DC Injection Brake
Mode
0: Current Mode
1 : Voltage Mode
1
-
*6
07-16
DC Injection Brake
Level (Voltage Mode)
0.0~10.0
4.0
-
*6
Group 08- Drive & Motor Protection Functions
No.
Description
Range
Factory
Setting
Unit
Note
08-00
Trip Prevention
Selection
xxxx0: Enable Trip Prevention During
Acceleration
xxxx1: Disable Trip Prevention During
Acceleration
xxx0x: Enable Trip Prevention During
Deceleration
xxx1x: Disable Trip Prevention During
Deceleration
xx0xx: Enable Trip Prevention in Run
Mode
xx1xx: Disable Trip Prevention in Run
Mode
x0xxx: Enable Over Voltage Prevention
in Run Mode
x1xxx: Disable Over Voltage Prevention
in Run Mode
01000
-
*5
08-01
Trip Prevention Level
During Acceleration (%)
50 ~ 200
200
%
1
08-02
Trip Prevention Level
During Deceleration (%)
50 ~ 200
200
08-03
Trip Prevention Level in
Run Mode (%)
50 ~ 200
200
08-04
Over Voltage
Prevention
350.0~390.0/700.0~780.0
380.0/7
60.0
VD
C
1
Base on the percentage of inverter rated current.