Group 08- Drive & Motor Protection Functions

No.

Description

Range

Factory

Setting

Unit

Note

Level in Run Mode

08-05

Electronic Motor
Overload Protection
Operation Mode

0: Disable
1: Enable

1

-

*7

08-06

Operation After
Overload Protection is
Activated

0: Coast-to-Stop After Overload Protection is

Activated

1: Drive Will Not Trip when Overload Protection

is Activated (OL1)

0

-

08-07

Over Heat Protection
( cooling fan control)

0: Auto (Depends on temp.)
1: Operate while in RUN Mode
2: Always Run
3: Disabled

1

-

08-08

AVR Function
(Auto Voltage
Regulation)

0: AVR Function Enable

4

-

*5

1: AVR Function Disable
2: AVR Function Disable for Stop
3: AVR Function Disable for Deceleration.
4: AVR Function Disabled for Stop and

Deceleration.

5: When VDC>360V, AVR Function is Disabled

for Stop and Deceleration.

08-09

Input Phase Loss
Protection

0: Disabled
1: Enabled

0

-

08-10

Output Phase Losts
Protection

0: Disabled

0

-

1: Enabled

08-11

Motor Type Selection

0: Overload protection (Standard Motor)

0

-

1: Overload protection (Inverter Duty Motor)

08-12

Motor Overload
Protection Curve

0: Motor Overload Protection for General loads

(OL=103 %) (150% for 1 Minutes)

0

-

1: Motor Over load Protection for HVAC ( Fan &

Pump) (OL=113%) (123% for 1 Minutes).

08-13

Over Torque Detection
Control

0: Over Torque Detection Disabled

0

-

1:

Over  torque  detection  after  set  frequency  is

reached

2:

Over torque detection after run command

08-14

Over torque protection
action

0: Stop Output After Over Torque Detection

(Free Run to Stop)

0

-

1:Continue Running After Over Torque
Detection (Display only OL3)

08-15

Over Torque Detection
Level

30~300

160

-

08-16

Over Torque Detection
Time

0.0~25.0

0.1

-

08-17

Fire Mode (for firmware
below v1.1)

0: Disabled.

0

-

*5

1: Enabled

08-18

Ground Fault Detection

0: Disabled

0

*7

1: Enabled

Notes:Regarding fire mode function, please refer to the conditions below,

1. Below firmware v1.1, Fire Mode is enabled by setting 08-17 = 1
2. Above (including) firmware v1.1, Fire Mode is enabled by setting digital inputs 03-00~03-05 = 28.

Parameter 08-17 is then removed.

3. 08-18 is applicable to frame 3 and 4 only.

Содержание EM16-123 F-20 Series

Страница 1: ...3 2 Single Three Phase 12 2 3 3 Three Phase 13 2 4 Terminal Description 14 2 4 1 Description of main circuit terminals 14 2 4 2 Control circuit terminal description 15 2 5 Outline Dimensions 16 2 5 1...

Страница 2: ...rsonal injury if misused Caution Indicates that the inverter or the mechanical system might be damaged if misused Danger Risk of electric shock The DC link capacitors remain charged for five minutes a...

Страница 3: ...ct provides the 24V for internal use only do not use as the power supply sources for other external components such as sensors electronic components etc otherwise it will cause adverse situation When...

Страница 4: ...the run FWD REV switch closed then the inverter will restart Danger Prior to use ensure that all risks and safety implications are considered When the momentary power loss ride through is selected and...

Страница 5: ...switched off before disassembling or checking any components 1 5 Inverter Disposal Caution Please dispose of this unit with care as an industrial waste and according to your required local regulation...

Страница 6: ...00V 400V inverter with rating below 15KW is connected to a high capacity power source 600KVA or above then an AC reactor can be connected for power factor improvement and reducing harmonics Input nois...

Страница 7: ...1850 EMI filter F integrated standard EMI filter A class C2 category IP degree 20 IP20 enclosure 66 IP66 enclosure Power supply 123 1ph 230V 340 3ph 400V Local command Blank No built in S Power Switc...

Страница 8: ...sure IP20 The input current is calculated value at full rated output current F Built in EMI filter 20 Protection class IP20 Type Enclosure IP66 Power switch on board Potentiometer on board Model EM16...

Страница 9: ...ry power loss time s 2 0 2 0 2 0 2 0 Enclosure IP20 The input current is calculated value at full rated output current Model EM16 340 F 20 0550 0750 1100 1500 1850 Recommended motor power KW 5 5 7 5 1...

Страница 10: ...2 5 2 5 Allowable momentary power loss time s 2 0 2 0 2 0 2 0 Enclosure IP66 Model EM16 340 F 66 S 0550 0750 1100 Recommended motor power KW 5 5 7 5 11 Rated output current A 13 0 17 5 24 Rated power...

Страница 11: ...on input 29 functions refer to description on group3 Multifunction output 21 functions refer to description on group3 Multifunction analog output 5 functions refer to description on group4 Main featur...

Страница 12: ...brake transistor Communication control Standard built in RS485 communication Modbus One to one or One to many control Environment Operating temperature 10 50 Note1 Storage temperature 20 60 Humidity...

Страница 13: ...13 2 3 Standard wiring 2 3 1 Single Phase Models EM16 123 0037 F EM16 123 0075 F EM16 123 0150 F EM16 123 0220 F...

Страница 14: ...4 2 3 3 Three phase Multifunction Input Terminals Models EM16 340 0075 F EM16 340 0150 F EM16 340 0220 F EM16 340 0400 F EM16 340 0550 F EM16 340 0750 F EM16 340 1100 F EM16 340 1500 F EM16 340 1850 F...

Страница 15: ...put single phase L1 L L3 N single three phase L1 L L2 L3 N three phase L1 L2 L3 L2 L3 N T1 Inverter output connect to U V W terminals of motor T2 T3 P Braking resistor connection terminal Used in appl...

Страница 16: ...al Loss Final count value reached Initial count value recahed PLC Status Indicator PLC control 250VAC 1A 30VDC 1A R1B NC Normally closed R1C COMMON R2A R2B 24VPower supply COM Digital signal common te...

Страница 17: ...5 1 IP20 dimensions Frame1 IP20 Single phase 230V 0 37 0 75 kW Three phase 400V 0 75 1 5 kW 2 Q1 2 Q2 W1 H1 H W2 W E D D1 Model Dimensions mm N W Kg W W1 W2 H H1 D D1 E Q1 Q2 EM16 123 0037 F 20 90 6 8...

Страница 18: ...e 400V 2 2 4 0 kW W1 H1 H2 W2 W 2 Q1 E D1 D D2 2 Q2 H Model Dimensions mm N W Kg W W1 W2 H H1 H2 D D1 D2 E Q1 Q2 EM16 123 0150 F 20 128 7 118 118 187 6 177 6 197 5 150 133 8 141 8 48 2 4 5 4 5 2 5 EM1...

Страница 19: ...400V 5 5 11 kW W1 H W D D1 D2 E W2 H2 2 Q1 H1 2 Q2 Model Dimensions mm N W Kg W W1 W2 H H1 H2 D D1 D2 E Q1 Q2 EM16 340 0550 F 20 186 9 175 176 260 9 249 8 273 197 2 184 189 76 7 4 5 4 5 6 7 EM16 340 0...

Страница 20: ...me4 IP20 Three phase 400V 15 18 5 kW Model Dimensions mm N W Kg W W1 W2 H H1 H2 D D1 D2 E1 E2 Q1 Q2 EM16 340 1500 F 20 224 6 207 20 436 303 5 330 9 200 7 187 5 192 5 64 192 5 6 6 13 7 EM16 340 1850 F...

Страница 21: ...0V 0 37 0 75 kW Three phase 400V 0 75 1 5 kW Model Dimensions mm N W Kg W W1 H H1 H2 D D1 D2 D3 Q1 Q2 Q3 EM16 123 0037 F 66 S 150 8 133 3 248 7 230 2 214 2 183 200 200 49 5 5 4 5 4 10 6 2 9 EM16 123 0...

Страница 22: ...1 5 2 2 kW Three phase 400V 2 2 4 kW Model Dimensions mm N W kg W W1 H H1 H2 D D1 D2 D3 Q1 Q2 EM16 123 0150 F 66 S 198 115 335 315 337 9 218 4 235 2 235 2 79 8 7 7 5 98 EM16 123 0220 F 66 S EM16 340...

Страница 23: ...IP66 Three phase 400V 5 5 18 5 kW Model Dimensions mm N W kg W W1 H H1 H2 D D1 D2 D3 Q1 Q2 EM16 340 0550 F 66 S 222 8 140 460 440 466 3 246 6 266 5 263 5 96 7 7 12 68 EM16 340 0750 F 66 S EM16 340 11...

Страница 24: ...frequency is displayed Variable Resistor FREQ SET Used to set the frequency Keys On Keypad 8 buttons RUN RUN Run at the set frequency STOP STOP Decelerate or Coast to Stop Increment parameter number...

Страница 25: ...d setup Group 08 Drive and motor Protection Group 09 Communication function setup Group 10 PID function setup Group 11 Performance control functions Group 12 Digital Display Monitor functions Group 13...

Страница 26: ...Keypad 2 External AI1Analog Signal Input 3 External AI2 Analog Signal Input 4 External Up Down Frequency Control 5 Communication Setting Frequency 6 PID Ouput Frequency 7 Pulse Input 6 00 07 Main and...

Страница 27: ...lts Hz Curve Modification Torque Boost 0 10 0 0 0 1 01 11 V F start Frequency 0 00 10 00 0 00 Hz 01 12 Slip compensation gain 0 05 10 00 0 10 S 01 13 V F Mode Select 0 Mode 0 1 Mode 1 by models 7 Grou...

Страница 28: ...eed Search 20 Energy Saving only V F 21 Reset PID integral value to Zero 22 Counter Input 23 Counter Reset 24 PLC Input 25 Pulse Input Width Measure S3 6 26 Pulse Input Frequenct Measure S3 6 27 Enabl...

Страница 29: ...03 13 Preset Frequency Reached Level 0 00 599 00 0 00 Hz 1 03 14 Frequency Reached Detection Range 0 00 30 00 2 00 Hz 1 03 15 Preset output current reached 0 1 15 0 0 1 A 03 16 Preset output Current d...

Страница 30: ...egative 0 1 04 05 AI1 Slope 0 Positive 1 Negative 0 1 04 06 AI2 Signal Verification Scan Rate 1 200 50 2ms 04 07 AI2 Gain 0 1000 100 1 04 08 AI2 Bias 0 100 0 1 04 09 AI2 Bias Selection 0 Positive 1 Ne...

Страница 31: ...5 Hz 0 00 Hz 1 05 17 Preset Speed0 Acctime 0 1 3600 0 10 0 Sec 1 05 18 Preset Speed0 Dectime 10 0 Sec 1 05 19 Preset Speed1 Acctime 10 0 Sec 1 05 20 Preset Speed1 Dectime 10 0 Sec 1 05 21 Preset Speed...

Страница 32: ...Of final step to run Continues to run from the unfinished step if restarted 4 Single cycle Starts a new cycle if restarted 5 Periodic cycle Starts a new cycle if restarted 6 Single cycle then hold th...

Страница 33: ...0 0 Sec 06 19 Auto_ Run Mode Running Time Setting 3 0 0 Sec 06 20 Auto_ Run Mode Running Time Setting 4 0 0 Sec 06 21 Auto_ Run Mode Running Time Setting 5 0 0 Sec 06 22 Auto_ Run Mode Running Time Se...

Страница 34: ...Direction 9 0 06 42 Auto_ Run Mode Running Direction10 0 06 43 Auto_ Run Mode Running Direction 11 0 06 44 Auto_ Run Mode Running Direction12 0 06 45 Auto_ Run Mode Running Direction13 0 06 46 Auto_...

Страница 35: ...Time 0 0 25 0 KEB Deceleration Time 0 0 Sec 07 15 DC Injection Brake Mode 0 Current Mode 1 Voltage Mode 1 6 07 16 DC Injection Brake Level Voltage Mode 0 0 10 0 4 0 6 Group 08 Drive Motor Protection F...

Страница 36: ...ion 0 Overload protection Standard Motor 0 1 Overload protection Inverter Duty Motor 08 12 Motor Overload Protection Curve 0 Motor Overload Protection for General loads OL 103 150 for 1 Minutes 0 1 Mo...

Страница 37: ...tion to Stop 00 17 Deceleration Time 2 3 Continue Operating 0 09 08 Comm Fault Tolerance Count 1 20 3 09 09 Wait Time of Inverter Transmission 5 65 5 ms Group 10 PID Function Setup No Description Rang...

Страница 38: ...Integral value Error Margin Units 1 Unit 1 8192 0 100 0 10 17 PID Sleep Frequency Level 0 00 599 00 0 00 Hz 10 18 PID Sleep Function Delay Time 0 0 25 5 0 0 Sec 10 19 PID Wake up frequency Level 0 00...

Страница 39: ...onitor Functions No Description Range Factory Setting Unit Note 12 00 Extended Display Mode 00000 88888 Each digit can be set from 0 to 8 as listed below 00000 1 0 Default Display Frequency and Parame...

Страница 40: ...trol Circuit Capacitors is Invalid xxx1x Life Alarm of Control Circuit Capacitors is Valid xx0xx Life Alarm of Main Circuit Capacitors is Invalid xx1xx Life Alarm of Main Circuit Capacitors is Valid 1...

Страница 41: ...Enable all Functions 1 Preset Speeds from 05 01 to 05 15 Can t be Changed 2 All Functions Can t be Changed Except for Preset speeds from 05 01 to 05 15 3 Disable All Functions Except 13 06 0 13 07 Par...

Страница 42: ...14 20 Setting Value1 of C5 0 65535 0 14 21 Setting Value1 of C6 0 65535 0 14 22 Setting Value1 of C7 0 65535 0 14 23 Setting Value1 of C8 0 65535 0 14 24 Setting Value1 of AS1 0 65535 0 14 25 Setting...

Страница 43: ...alue of T7 0 9999 0 15 13 Current Value of T7 mode 7 0 9999 0 15 14 Current Value of T8 0 9999 0 15 15 Current Value of T8 mode 7 0 9999 0 15 16 Current Value of C1 0 65535 0 15 17 Current Value of C2...

Страница 44: ...o result then replace the inverter EPr EEPROM problem Faulty EEPROM Consult with the supplier COt Communication error Communication disruption Check the wiring CtEr Current Sensor detection error Curr...

Страница 45: ...cation LF Output phase loss Loss of output voltage on any of the phases 1 Check output cable connection 2 Determine resistance between the lines 3 Check whether the terminals are loose Faults which ca...

Страница 46: ...00 Err1 Keypad operation error 1 Press or while 00 05 00 06 0 or running at preset speed 2 Attempt to modify the Parameter Can not be modified during operation refer to the parameter list 1 The or is...

Страница 47: ...se and re activate the run contact to restart the inverter E S External Rapid stop When external rapid stop input is activated the inverter will decelerate to stop and the display will flash with E S...

Страница 48: ...y excessively 1 Minimize the variation of the load 2 Consider increasing the capacities of the inverter and the motor Is the input power erratic or is there a phase loss 1 Consider adding an AC reacto...

Отзывы: