36
Group 08- Drive & Motor Protection Functions
No.
Description
Range
Factory
Setting
Unit
Note
Level in Run Mode
08-05
Electronic Motor
Overload Protection
Operation Mode
0: Disable
1: Enable
1
-
*7
08-06
Operation After
Overload Protection is
Activated
0: Coast-to-Stop After Overload Protection is
Activated
1: Drive Will Not Trip when Overload Protection
is Activated (OL1)
0
-
08-07
Over Heat Protection
( cooling fan control)
0: Auto (Depends on temp.)
1: Operate while in RUN Mode
2: Always Run
3: Disabled
1
-
08-08
AVR Function
(Auto Voltage
Regulation)
0: AVR Function Enable
4
-
*5
1: AVR Function Disable
2: AVR Function Disable for Stop
3: AVR Function Disable for Deceleration.
4: AVR Function Disabled for Stop and
Deceleration.
5: When VDC>360V, AVR Function is Disabled
for Stop and Deceleration.
08-09
Input Phase Loss
Protection
0: Disabled
1: Enabled
0
-
08-10
Output Phase Losts
Protection
0: Disabled
0
-
1: Enabled
08-11
Motor Type Selection
0: Overload protection (Standard Motor)
0
-
1: Overload protection (Inverter Duty Motor)
08-12
Motor Overload
Protection Curve
0: Motor Overload Protection for General loads
(OL=103 %) (150% for 1 Minutes)
0
-
1: Motor Over load Protection for HVAC ( Fan &
Pump) (OL=113%) (123% for 1 Minutes).
08-13
Over Torque Detection
Control
0: Over Torque Detection Disabled
0
-
1:
Over torque detection after set frequency is
reached
2:
Over torque detection after run command
08-14
Over torque protection
action
0: Stop Output After Over Torque Detection
(Free Run to Stop)
0
-
1:Continue Running After Over Torque
Detection (Display only OL3)
08-15
Over Torque Detection
Level
30~300
160
-
08-16
Over Torque Detection
Time
0.0~25.0
0.1
-
08-17
Fire Mode (for firmware
below v1.1)
0: Disabled.
0
-
*5
1: Enabled
08-18
Ground Fault Detection
0: Disabled
0
*7
1: Enabled
Notes:Regarding fire mode function, please refer to the conditions below,
1. Below firmware v1.1, Fire Mode is enabled by setting 08-17 = 1
2. Above (including) firmware v1.1, Fire Mode is enabled by setting digital inputs 03-00~03-05 = 28.
Parameter 08-17 is then removed.
3. 08-18 is applicable to frame 3 and 4 only.