8 SETTINGS VIA THE MICT
50
Rev. 07/2013
Settings of the input selected
Analog Inputs (Current or Voltage)
Based on the values used by your master control, you can define the values
of the open and the closed position for the analog inputs in the MICT. The
value applied on the input will then be converted to the relevant opening
angle of the fuel ring proportional to the values entered.
Example:
Your master control works with a power input of 4 to 20 mA. In the MICT,
you configure 4 mA to refer to the closed position and 20 mA to the open
position. If the current on the input is now 16 mA, the fuel ring will be 75%
open.
Digital Inputs
In the MICT, you can define the behavior for the digital inputs
DIRin
and
STEPSin
. The level at
DIRin
determines the direction in which the fuel ring
will move if there are pulse signals at
STEPSin
.
Example:
You have selected the option
High -> Open
in the MICT under
Direction
. If a
high level is now present on
DIRin
, one step will be added to the current
position with each pulse signal received at
STEPSin
. The fuel ring will then
move gradually from the closed to the open direction.
Unused inputs and outputs
Please note that the terminals for the analog inputs and outputs not
selected in the MICT must remain unoccupied.