![Motortech Varistep Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/motortech/varistep/varistep_operating-manual_1839340049.webp)
Rev. 07/2013
49
Input Voltage/Input Current
Depending on which input is selected, you have different adjustment options available. For the
analog inputs, please enter the values for the open and closed position of the fuel ring. Here,
please adhere to the following values:
–
Input voltage: 0 to 10 V
–
Input current: 0 to 20 mA
Input Step Count/Step Count Configuration
Set the
Direction
and
Init Position
of the steps. The initial position (=
Init Position
) will be
approached after the reference run of the stepper motor.
To make these settings, please refer to all additional information as provided in the following
note.
Click this button to apply the settings of the analog input (current or voltage) to the output
selected. If you have selected another input as an output (e. g. input: current; output: voltage),
the adjusted values are converted in accordance with the output's value range.
Output Voltage/Output Current
Depending on the relevant selection, enter the relevant current or voltage values, which
correspond to the open and closed position of the fuel ring. Here, the same value ranges are
applicable as with the analog inputs.