9.2.2.4
Analog Outputs
The
Analog Outputs
button in the
Preferences
view of an added I/O communication module
opens the
Analog Outputs
view.
Note that changes in this view are not saved and applied by the I/O communication module until
you exit the view. Use the drop-down list to link the analog output of the I/O communication
module displayed in the
Ch.
(Channel) column to the following functions:
–
Not Used
The analog output input is not linked to any function.
–
Average NO
X
from NOx1 / NOx2
Output of the provisional daily average of nitrogen oxide readings converted according to
VDMA 6299:2019-09 (see section
Conversion of Nitrogen Oxide Readings
on page 42) as
determined by the respective NO
X
monitor. Scaling: 4 mA correspond to 0 mg/Nm³, 20 mA
correspond to 1,000 mg/Nm³.
–
Actual NO
X
from NOx1 / NOx2
Output of the nitrogen oxide reading currently measured by the respective NO
X
monitor con-
verted according to VDMA 6299:2019-09. Scaling: 4 mA correspond to 0 mg/Nm³, 20 mA cor-
respond to 1,000 mg/Nm³.