9 Devices
114
Rev. 06/2021
–
---
In NO
X
monitoring modes
Off
and
Recording Only
, normal operation detection is dis-
abled. In the NO
X
monitoring mode
Start/Stop via CANopen
, the NO
X
monitor receives
the normal operation release from the master control.
–
K
Enter the NO
2
/NO
X
ratio of the exhaust gas from your system. The NO
2
/NO
X
ratio must be de-
termined at the mounting position of the NO
X
sensor's sensing element before start-up of
NO
X
monitoring and each time the NO
X
sensor is replaced. More information on this is avail-
able in the section
Determining the NO
2
/NO
ₓ
Ratio
–
KNO
2
Enter the factor for the corrective calculation of the NO
X
sensor's NO
2
sensitivity. For the cor-
rection factor, refer to the entry
NO
2
Gain
in the
NO
X
Sensor
view (see section
Sensor
on
–
Level Limit
Enter the daily average of the NO
X
concentration, which must not be exceeded under any cir-
cumstances. To use the NO
X
monitoring of the EasyNO
ₓ
in accordance with standard sheet
VDMA 6299:2019-09, enter here the daily average at which an alarm should be triggered. If
the daily average exceeds the level limit at the end of a day, the detected normal operation
hours are added to the failure hour counter of the ongoing calendar year. The change of day
is firmly preset to 0:00 hrs Central European Time (CET) or UTC+1.
–
Level Warning
Below the configured
Level Limit
, specify a daily average of the NO
X
concentration above
which the EasyNO
ₓ
will issue a warning. The
Level Warning
daily average serves to indicate
that the daily average is approaching the configured level limit. As a warning threshold, you
can specify your currently valid plant-specific limit value.
–
Time Limit
For the failure hour counter of the NO
X
monitor, specify a time threshold that the NO
X
con-
centration may exceed the configured level limit as a maximum within one calendar year. If
this time threshold is exceeded, the EasyNO
ₓ
indicates this in the
NO
X
Monitoring
view in the
failure hour counter
Alm
via a red status display.
–
Time Warning
For the failure hour counter of the NO
X
monitor, specify a warning threshold to indicate that
the failure hour counter is approaching the configured
Time Limit
. If this warning threshold
is exceeded, the EasyNO
ₓ
indicates this in the
NO
X
Monitoring
view in the failure hour
counter
Alm
via a yellow status display.
–
Name
Enter a custom name for the engine to be monitored. This name is displayed in the title area
in all views of the respective NO
X
monitor.
–
Serial Number
Enter the serial number of the engine to be monitored. This field is mandatory.
Содержание EasyNOx
Страница 1: ...EasyNOX NOX Monitoring Operating Manual P N 01 50 026 EN Rev 06 2021 ...
Страница 33: ...4 Product Description Rev 06 2021 33 4 1 7 Overview Drawings 4 1 7 1 Dimensions EasyNOX ...
Страница 34: ...4 Product Description 34 Rev 06 2021 ...
Страница 35: ...4 Product Description Rev 06 2021 35 CAN Bus NOX Sensor Module P N 63 05 015 ...
Страница 36: ...4 Product Description 36 Rev 06 2021 I O Communication Module Optional ...
Страница 142: ......