![Motortech EasyNOx Скачать руководство пользователя страница 115](http://html1.mh-extra.com/html/motortech/easynox/easynox_operating-manual_1839341115.webp)
9 Devices
Rev. 06/2021
115
–
Layout
Use the drop-down list to set the layout of the thermocouples (see
Installation Locations of
Thermocouples
–
Before & After Cat
One thermocouple respectively measures the exhaust gas temperature before and after
the catalytic converter.
–
One After Cat
One thermocouple measures the exhaust gas temperature after the catalytic converter.
–
Two After Cat
In engines with two exhaust gas lines, one thermocouple after each catalytic converter
measures the exhaust gas temperature.
–
Overtemperature 1 / 2
Specify respectively the exhaust gas temperature which must not be exceeded in the ex-
haust pipe at the corresponding measuring point (
1
=T1,
2
=T2).
–
Undertemperature 1 / 2
Specify respectively the exhaust gas temperature which must not be undercut in the exhaust
pipe at the corresponding measuring point (
1
=T1,
2
=T2).
–
Min. Δ Temperature, Max. Δ Temperature
If you have selected the layout
Before & After Cat
for exhaust gas temperature monitoring,
you must also specify the permissible temperature difference range of the exhaust gas be-
tween the catalyst inlet and outlet. A positive temperature difference stands for a corre-
spondingly higher temperature at the outlet compared to the inlet. A negative temperature
difference stands for a correspondingly lower temperature at the outlet compared to the
inlet.
Содержание EasyNOx
Страница 1: ...EasyNOX NOX Monitoring Operating Manual P N 01 50 026 EN Rev 06 2021 ...
Страница 33: ...4 Product Description Rev 06 2021 33 4 1 7 Overview Drawings 4 1 7 1 Dimensions EasyNOX ...
Страница 34: ...4 Product Description 34 Rev 06 2021 ...
Страница 35: ...4 Product Description Rev 06 2021 35 CAN Bus NOX Sensor Module P N 63 05 015 ...
Страница 36: ...4 Product Description 36 Rev 06 2021 I O Communication Module Optional ...
Страница 142: ......