AUXILIARY GENERATION IN AC 230V/50Hz
The auxiliary output is drawn by means of a 3 pole socket, the
two poles are live, phase and neutral, plus the earth for the
machine.
The single phase generation of the machine was designed
to supply small power tools (grinders, drills etc.) to assist the
welding operations with a quick, safe connection without the
need to connect to earth. In addition, supplying only one tool
at a time, the protection against indirect contact is assured by
“electrical separation”.
Therefore, the machine MUST NOT be intentionally connected
to earth, attaching cables must be of 3 wires and the electrical
equipment on which it being used must have an extension length
limited to 100-200 metres. This limitation of circuit extension
length is fundamental for safety.
The cables must be SUITED to the environment in which they
are to be used. Bear in mind that at temperatures below 5°C
PVC cables become rigid and the PVC insulation tends to split
at the first crease.
Using double insulated equipment is advisable, this is
identifiable by the symbol and for having no earth facility.
If the machine is designed to supply circuits which are
particularly complex or in an area with potential electrical risk, it
is required to interpose a complete electrical distribution panel,
equipped with all electrical protections required, between the
plug and loads.
For example: you can use a distribution system TN-S. In this
case one of the phases, used as a neutral must be grounded;
a bipolar 30mA differential switch (GFI) must be mounted
inside the electrical box, before the sockets to which loads are
connected; the terminal in the frontal panel of the generating
set near the socket is to be used as earth connection, wiring
it to the ground of the electrical plant with which the machine
is going to work.
WARNING
: bound the neutral to frame BEFORE the GFI.
M
37
USE AS A GENERATOR
REV
.0-12/19
WARNING
It is absolutely forbidden to connect the unit to the public
mains and/or another electrical power source.
Areas for which access by non-authorized personnel is
for-
bidden
are: - the control panel (at the front) - the endothermic
motor discharge.
!