7

TRUNKGUARD 

®

 Fieldbus

Power Supply

TPS400

SPM201 Surge Protection Module

Surge Protection Modules (optional component) fi t 
onto the fi eld-side pluggable socket on the DIN Carrier 
face and accept the fi eld-side pluggable terminals.  
They only mount in one orientation.  A long screw 
is provided to secure the unit to the Carrier.  This 
screw must be fi tted in order to complete the ground 
connection of the Surge Protection Module. 

Device Coupler

The TPS400 can supply conditioned power to any 
suitably certifi ed fi eldbus device coupler (also spur 
junction block, brick, etc.) including the MooreHawke 
TG200 and TG300 TRUNKGUARD Series, the 
SPURBARRIER™ Series, and third-party device 
couplers.  Please consult the appropriate device 
coupler manual for installation instructions 

Wiring Connections

Any cable suitable for FOUNDATION fi eldbus / 
PROFIBUS PA applications may be used.  This is 
typically 6-22 AWG cable with individual shields 
(normally called Type A cable).  Components from 
multiple segments may be combined within a 
multi-core cable.  It is recommended that various 
component shields remain independent of each other 
within the multi-core cable.

Wire terminations should be made from cables 
stripped to expose no more than 8mm (0.3 in) of 
conductor and inserted fully into the terminal opening.  
Bootlace ferrules are recommended for use with 
stranded cable.  

Field-side segment wiring is made via screw-
clamp pluggable terminals marked FIELD.  HOST 
connections are made either through the terminals 
marked HOST or via multi-way cables plugged 
directly to the HOST connectors on the Carrier.  See 
Appendices for HOST specifi c hook up information.

Nominal 24Vdc (19.2-30Vdc) power is required for 
terminals marked DC Power.  Provisions are made for 
two independent DC feeds to the Carrier. 

WARNING:

To avoid an explosion hazard

 

do not 

disconnect equipment at trunk terminals when 

a fl ammable or combustible atmosphere is 

present.

Note: 

If only one DC power input is to be used, 

the FMD252 (if fi tted) will indicate an alarm. 

Hence, use a pair of jumper wires between 

both DC inputs A and B terminals to insure it 

operates correctly. 

Once all wiring connections have been made, all 
retaining screws on each module should be securely 
fastened and any external enclosure closed (where 
applicable).

Terminator

Each Segment must have two terminators to function 
properly.  The terminator (100 ohm resistor in series 
with a 1 microfarad capacitor) provides an end load 
for the segment and prevents refl ections.  A terminator 
is hard wired on the TPS400 carrier board for each 
segment.  Another terminator should be placed at the 
end of the segment in the fi eld (if using a TG Series 
device coupler with an auto-termination feature the 
second terminator will automatically be applied).

Contact MooreHawke if the HOST link cable is in 
excess of 30m (100ft).

Содержание TRUNKGUARD TPS400

Страница 1: ...TPS400 May 2016 206 791 00C TRUNKGUARD Fieldbus Power Supply TRUNKGUARD Fieldbus Power Supply TPS400...

Страница 2: ...nections 7 Terminator 7 Grounding 8 Case Ground 8 Shield Ground 8 Surge Ground 8 Recommended Ground Wiring Practices 8 Testing and Troubleshooting 9 LED Operation 9 CE Conformity 10 Operation 10 Maint...

Страница 3: ...odules for each segment Modules are hot swappable with load sharing in redundant pairs to maintain power to the segment in the instance that one module in a pair needs to be removed Universal Modules...

Страница 4: ...mal ORANGE Out put Voltage 18V LED Short GREEN normal RED Cable Short LED Open GREEN normal RED Carrier Fault FDM252 Fieldbus Diag nostics Module Power Dissipation 0 5W maximum LED Type GREEN Normal R...

Страница 5: ...Figure 2 Dimensions for The TRUNKGUARD TPS401 Simplex Dimensions 114mm 4 50in TPS401 4D TPS401 4Y 300mm 8 5in TPS400 121mm 4 75in Figure 3 Dimensions for The TRUNKGUARD TPS402 Duplex 114mm 4 50in 356...

Страница 6: ...e on board screws to secure the module to the Carrier Fieldbus Diagnostics Modules are required for alarm indication and alarm contact output but removal or non installation does not affect the power...

Страница 7: ...re recommended for use with stranded cable Field side segment wiring is made via screw clamp pluggable terminals marked FIELD HOST connections are made either through the terminals marked HOST or via...

Страница 8: ...onnected to the normal SHIELD ground When used for surge protection the shorting bar between these ground points must be removed Therefore if no surge protection is being used this shorting bar must b...

Страница 9: ...OISE 2 NOISE 3 NOISE 4 LED Indication GREEN RED OFF Normal Operation Input Voltage A 18V Module failure GREEN RED OFF Normal Operation Input Voltage B 18V Module failure GREEN RED OFF Normal Operation...

Страница 10: ...quirements for programmed maintenance TPS400 Series modules contain no user serviceable parts Non functioning units under warranty should be returned to Moore Industries for replacement or repair Moor...

Страница 11: ...D 800HSE FDM252 Segment 2 Segment 3 Segment 4 Segment 2 Segment 3 Segment 4 TPS400 Segment 1_1A Fieldbus Cable Fieldbus Cable Fieldbus Cable Control Network HSE Subnet Server AC 800M LD 800HSE LD 800H...

Страница 12: ...utilizes Series 2 H1 cards To install TRUNKGUARD with an Emerson DeltaV system refer to Figure A 2 Segment 1_1A Emerson Series 2 H1 Card Series 2 H1 Card FDM252 Segment 2 Segment 3 Segment 4 TPS400 S...

Страница 13: ...System Configuration To utilize TRUNKGUARD with a Yokogawa CENTUM system refer to Figure A 3 below AKB336 AKB336 AKB336 FDM252 TPS400 FDM252 Segment 2 Segment 2 Segment 3 Segment 4 Segment 3 Segment...

Страница 14: ...the TPS 400 Carrier board Refer to Figure A 4 below FDM252 Segment 2 Segment 3 Segment 4 TPS400 DB37 DB25 Cable DB37 DB25 Cable FDM252 Segment 2 Segment 3 Segment 4 Simplex TPS401 4D Duplex TPS402 4D...

Страница 15: ...implex TPS401 4D Duplex TPS402 4D Honeywell Series C FIM 1 2 3 4 SEGMENT 1 SEGMENT 1 Honeywell Series C FIM 1 2 3 4 DB25 16 pin Cable Segments 1 4 Multi Segments with alarm connections P N 804 013 26...

Страница 16: ...BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT BE L...

Отзывы: