background image

TRUNKGUARD 

®

 Fieldbus

Power Supply

TPS400

Grounding

The TPS400 carrier is provided with three independent 
connection points relating to ground.  This section 
provides details of each connection point and provides 
recommendations on connecting these grounds.

Case Ground

The CASE ground connection is for personnel 
protection and should be connected to the local 
structural ground in the panel or enclosure, typically 
the incoming ac power ground, if available.  The case 
can also be grounded via the DIN rail.

Shield Ground

The SHIELD ground is the collection point for all of 
the shields relating to the fi eldbus signals (both fi eld  
and HOST-side).  This may be directly connected to 
ground, through a capacitor or via the HOST ground.

Note: 

If capacitor is not used, only one SHIELD 

ground is needed either at the power carrier 

or at the HOST top end. However, if it is at the 

power carrier, then connect SHIELD point to 

GROUND.

Surge Ground

The SURGE ground is available for those installations 
that use the SPM201 surge protection modules. 
These are designed to divert very large/short duration 
currents associated with surges (up to 20kA) and so 
these should not be connected to the normal SHIELD 
ground.  When used for surge protection, the shorting 
bar between these ground points must be removed. 
Therefore, if no surge protection is being used, this 
shorting bar must be always connected to ground.

Case Ground

Shorting Bar

Shield Ground

Surge Ground

Figure 5.

  Grounding options

Recommended Ground Wiring 
Practices 

Moore Industries recommends the following ground 
wiring practices: 

• Any Moore Hawke product in a metal case or 
housing should be grounded.

• The protective earth conductor must be 
connected to a system safety earth ground 
before making any other connections.

• All input signals to, and output signals from, 
MooreHawke’s products should be wired using 
a shielded, twisted pair technique.  Shields 
should be wired to the connector for the 
specifi c trunk or spur and the SHIELD ground 
connected as described above.

• The maximum length of unshielded input and 
output signal wiring should be 2 inches.

Fieldbus cable shields are “carried through” the 
TPS400 Carrier’s input/output terminals and require a 
suitable, noise-free ground connection point.

If SPM201 Surge Protection Units are fi tted, their 
securing screw must be installed per unit and the 
TPS400 DIN Carrier must be connected to a low 
impedance surge protection ground with a direct cable 
of at least 10 AWG (10mm

2

 cross-sectional area) from 

the grounding lug provided.

Содержание TRUNKGUARD TPS400

Страница 1: ...TPS400 May 2016 206 791 00C TRUNKGUARD Fieldbus Power Supply TRUNKGUARD Fieldbus Power Supply TPS400...

Страница 2: ...nections 7 Terminator 7 Grounding 8 Case Ground 8 Shield Ground 8 Surge Ground 8 Recommended Ground Wiring Practices 8 Testing and Troubleshooting 9 LED Operation 9 CE Conformity 10 Operation 10 Maint...

Страница 3: ...odules for each segment Modules are hot swappable with load sharing in redundant pairs to maintain power to the segment in the instance that one module in a pair needs to be removed Universal Modules...

Страница 4: ...mal ORANGE Out put Voltage 18V LED Short GREEN normal RED Cable Short LED Open GREEN normal RED Carrier Fault FDM252 Fieldbus Diag nostics Module Power Dissipation 0 5W maximum LED Type GREEN Normal R...

Страница 5: ...Figure 2 Dimensions for The TRUNKGUARD TPS401 Simplex Dimensions 114mm 4 50in TPS401 4D TPS401 4Y 300mm 8 5in TPS400 121mm 4 75in Figure 3 Dimensions for The TRUNKGUARD TPS402 Duplex 114mm 4 50in 356...

Страница 6: ...e on board screws to secure the module to the Carrier Fieldbus Diagnostics Modules are required for alarm indication and alarm contact output but removal or non installation does not affect the power...

Страница 7: ...re recommended for use with stranded cable Field side segment wiring is made via screw clamp pluggable terminals marked FIELD HOST connections are made either through the terminals marked HOST or via...

Страница 8: ...onnected to the normal SHIELD ground When used for surge protection the shorting bar between these ground points must be removed Therefore if no surge protection is being used this shorting bar must b...

Страница 9: ...OISE 2 NOISE 3 NOISE 4 LED Indication GREEN RED OFF Normal Operation Input Voltage A 18V Module failure GREEN RED OFF Normal Operation Input Voltage B 18V Module failure GREEN RED OFF Normal Operation...

Страница 10: ...quirements for programmed maintenance TPS400 Series modules contain no user serviceable parts Non functioning units under warranty should be returned to Moore Industries for replacement or repair Moor...

Страница 11: ...D 800HSE FDM252 Segment 2 Segment 3 Segment 4 Segment 2 Segment 3 Segment 4 TPS400 Segment 1_1A Fieldbus Cable Fieldbus Cable Fieldbus Cable Control Network HSE Subnet Server AC 800M LD 800HSE LD 800H...

Страница 12: ...utilizes Series 2 H1 cards To install TRUNKGUARD with an Emerson DeltaV system refer to Figure A 2 Segment 1_1A Emerson Series 2 H1 Card Series 2 H1 Card FDM252 Segment 2 Segment 3 Segment 4 TPS400 S...

Страница 13: ...System Configuration To utilize TRUNKGUARD with a Yokogawa CENTUM system refer to Figure A 3 below AKB336 AKB336 AKB336 FDM252 TPS400 FDM252 Segment 2 Segment 2 Segment 3 Segment 4 Segment 3 Segment...

Страница 14: ...the TPS 400 Carrier board Refer to Figure A 4 below FDM252 Segment 2 Segment 3 Segment 4 TPS400 DB37 DB25 Cable DB37 DB25 Cable FDM252 Segment 2 Segment 3 Segment 4 Simplex TPS401 4D Duplex TPS402 4D...

Страница 15: ...implex TPS401 4D Duplex TPS402 4D Honeywell Series C FIM 1 2 3 4 SEGMENT 1 SEGMENT 1 Honeywell Series C FIM 1 2 3 4 DB25 16 pin Cable Segments 1 4 Multi Segments with alarm connections P N 804 013 26...

Страница 16: ...BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT BE L...

Отзывы: