TRUNKGUARD 

®

 Fieldbus

Power Supply

TPS400

Introduction

The TRUNKGUARD TPS400 Power Supply enables 
fast and easy implementation of fi eldbus systems 
by providing properly conditioned power for simplex 
and duplex FOUNDATION fi eldbus H1 networks.  
TRUNKGUARD TPS400 is FOUNDATION fi eldbus 
registered and fully compliant with FF831-1 (the 
technical specifi cation for fi eldbus power supplies).

TRUNKGUARD TPS400 is composed of a DIN Carrier 
populated with individual Power Conditioner Modules 
(TPS202/TPS205).  A Fieldbus Diagnostics Module 
(FDM252) may be fi tted onto the DIN Carrier to 
provide alarm and diagnostics information.  It provides 
LED indicators for DC power status, cable short-
circuits and noise on each segment, and a common 
contact closure (opens on alarm).  The TPS202 
and FDM252 are also used in the Fault Tolerant 
TRUNKSAFE system.

Another component of the TRUNKGUARD TPS400 is 
the optional Surge Protection Module, SPM201, which 
provides a full 3-element surge suppression circuit for 
the selected segment.  The SPM201 fi ts directly onto 
the DIN Carrier pluggable terminal socket (fi eld-side) 
for the segment being protected.  This eliminates the 
need for additional panel wiring or mounting space.  
A ground connection for surge protection is provided 
through a bus bar located within the DIN Carrier.  It 
is made externally available as a separate grounding 
stud.

Features

• 

Delivers up to 500mA per segment.

  Available 

models supply 350mA (for non-incendive, energy- 
limited applications) or 500mA (for high current 
demand applications) of isolated, conditioned 
simplex (non-redundant) or duplex (redundant) 
power for up to four segments.  

• 

High-availability, modular design. 

 Provides 

individual power conditioner modules for each 
segment.  Modules are hot-swappable with load-
sharing in redundant pairs to maintain power to the 
segment in the instance that one module in a pair 
needs to be removed.

• 

Universal Modules.

  Power conditioner and other 

modules can be used in simplex, duplex and fault 
tolerant confi gurations.

• 

Economical fi eldbus physical layer diagnostics.  

An optional Diagnostics Module (FDM252) provides 
a master alarm and LED-based alarms for segment 
noise, DC voltage levels and conditioner status 
faults.

• 

Pluggable surge protection (optional).  

Surge 

protection with a three-element surge arrestor is 
available per segment to protect the TPS400 and the 
HOST from surges coming in on the trunk cables.

Figure 1.

  The TRUNKGUARD TPS400 provides duplex (redundant) or simplex power to each fi eldbus segment (duplex unit shown).

T

24DC 

Power 

Input “B”

Integral Fieldbus

Termination

Fieldbus
Devices

Fieldbus

Device Coupler

Fieldbus
Trunk In

Fieldbus

Trunk Out

Host

Input

Additional 

Fieldbus 

Device 

Couplers

24DC 

Power 

Input “A”

Additional Fieldbus H1 Segment Trunks

MooreHawke

TRUNKGUARD Series (TG200 and TG300)

SPURBARRIER Series

or

Third-Party

Optional

Removable 

Surge 

Protection

Modules 

(SPM201)

Redundant

24Vdc

Power Supply

Inputs

Diagnostic Master Alarm

Contact Closure

(Failsafe, Open on Alarm)

Optional 

Fieldbus Diagnostics 

Module (FDM252)

LEDs and Master 

Alarm Indicate:

24DC “A” Input Voltage Low
24DC “B” Input Voltage Low

Segment #1-4 Noise High

Power  Conditioner Alarm

 

HOST

Specific

H1 Connectors

Universal Plug-In Power 
Conditioner Module

TPS202 (350mA) is Compatible 
with TRUNKGUARD (TPS401/TPS402) 
and TRUNKSAFE (TPS201) DIN Carriers

TPS205 (500mA) is Compatible 
with TRUNKGUARD (TPS401/ TPS402) 
DIN Carrier

Duplex Configuration Shown

FIELDBUS NETWORK

Shield, Surge 
and Case
Grounds

Diagnostic 
LEDs Indicate:

Carrier Fault
Host or Field Cable Short Circuit
High Field Current (>Current Rating)
Low Module Output Voltage (<18V)

 

Содержание TRUNKGUARD TPS400

Страница 1: ...TPS400 May 2016 206 791 00C TRUNKGUARD Fieldbus Power Supply TRUNKGUARD Fieldbus Power Supply TPS400...

Страница 2: ...nections 7 Terminator 7 Grounding 8 Case Ground 8 Shield Ground 8 Surge Ground 8 Recommended Ground Wiring Practices 8 Testing and Troubleshooting 9 LED Operation 9 CE Conformity 10 Operation 10 Maint...

Страница 3: ...odules for each segment Modules are hot swappable with load sharing in redundant pairs to maintain power to the segment in the instance that one module in a pair needs to be removed Universal Modules...

Страница 4: ...mal ORANGE Out put Voltage 18V LED Short GREEN normal RED Cable Short LED Open GREEN normal RED Carrier Fault FDM252 Fieldbus Diag nostics Module Power Dissipation 0 5W maximum LED Type GREEN Normal R...

Страница 5: ...Figure 2 Dimensions for The TRUNKGUARD TPS401 Simplex Dimensions 114mm 4 50in TPS401 4D TPS401 4Y 300mm 8 5in TPS400 121mm 4 75in Figure 3 Dimensions for The TRUNKGUARD TPS402 Duplex 114mm 4 50in 356...

Страница 6: ...e on board screws to secure the module to the Carrier Fieldbus Diagnostics Modules are required for alarm indication and alarm contact output but removal or non installation does not affect the power...

Страница 7: ...re recommended for use with stranded cable Field side segment wiring is made via screw clamp pluggable terminals marked FIELD HOST connections are made either through the terminals marked HOST or via...

Страница 8: ...onnected to the normal SHIELD ground When used for surge protection the shorting bar between these ground points must be removed Therefore if no surge protection is being used this shorting bar must b...

Страница 9: ...OISE 2 NOISE 3 NOISE 4 LED Indication GREEN RED OFF Normal Operation Input Voltage A 18V Module failure GREEN RED OFF Normal Operation Input Voltage B 18V Module failure GREEN RED OFF Normal Operation...

Страница 10: ...quirements for programmed maintenance TPS400 Series modules contain no user serviceable parts Non functioning units under warranty should be returned to Moore Industries for replacement or repair Moor...

Страница 11: ...D 800HSE FDM252 Segment 2 Segment 3 Segment 4 Segment 2 Segment 3 Segment 4 TPS400 Segment 1_1A Fieldbus Cable Fieldbus Cable Fieldbus Cable Control Network HSE Subnet Server AC 800M LD 800HSE LD 800H...

Страница 12: ...utilizes Series 2 H1 cards To install TRUNKGUARD with an Emerson DeltaV system refer to Figure A 2 Segment 1_1A Emerson Series 2 H1 Card Series 2 H1 Card FDM252 Segment 2 Segment 3 Segment 4 TPS400 S...

Страница 13: ...System Configuration To utilize TRUNKGUARD with a Yokogawa CENTUM system refer to Figure A 3 below AKB336 AKB336 AKB336 FDM252 TPS400 FDM252 Segment 2 Segment 2 Segment 3 Segment 4 Segment 3 Segment...

Страница 14: ...the TPS 400 Carrier board Refer to Figure A 4 below FDM252 Segment 2 Segment 3 Segment 4 TPS400 DB37 DB25 Cable DB37 DB25 Cable FDM252 Segment 2 Segment 3 Segment 4 Simplex TPS401 4D Duplex TPS402 4D...

Страница 15: ...implex TPS401 4D Duplex TPS402 4D Honeywell Series C FIM 1 2 3 4 SEGMENT 1 SEGMENT 1 Honeywell Series C FIM 1 2 3 4 DB25 16 pin Cable Segments 1 4 Multi Segments with alarm connections P N 804 013 26...

Страница 16: ...BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT BE L...

Отзывы: