background image

18   The Interface Solution Experts

Programmable Isolated 
Thermocouple Transmitter

TIY

Making the Electrical Connections

The TIY is a loop-powered instrument.  The terminals 
for the power connections are marked “+PS” and 
“–PS”.  The input connections are marked “+IN” and 
“–IN”.

When the input to the TIY is a thermocouple (T/C), 
thermocouple wire must be used for the input 
connections.  If the input is other than a thermocouple, 
thermocouple wire is not required.

Figure 6 is a typical installation hookup diagram of 
the TIY.  Note the polarity of the wiring connections.

Recommended Ground Wiring Practices

Moore Industries recommends the following ground 

wiring practices:

• 

Any Moore Industries product in a metal case 

or housing should be grounded.

• 

The protective earth conductor must be 

connected to a system safety earth ground 

before making other connections.

• 

All input signals to, and output signals from, 

Moore Industries’ products should be wired 

using a shielded, twisted pair wiring technique. 

Shields should be connected to an earth or 

safety ground.

• 

For the best shielding, the shield should be 

run all the way from the signal source to the 

receiving device. (see Note below)

• 

The maximum length of un-shielded input and 

output signal wiring should be 2 inches.

Note:  

Some of Moore Industries’ instruments can be 

classified as receivers (IPT

2

, IPX

2

, etc.) and some 

can be classified as transmitters (TRX, TRY, etc.) 

while some are both a receiver and a transmitter 

(SPA

2

, HIM, etc).  Hence, your shield ground con-

nections should be appropriate for the type of signal 

line being shielded.  The shield should be grounded 

at the receiver and not at the signal source.

CE Conformity

Installation of any Moore Industries products that 
carry the CE certification (Commission Electrotech-
nique) must adhere to the guidelines above in order 
to meet the requirements set forth in applicable 
EMC (Electromagnetic Compatibility) directive 
2004/108/EC and specifications laid out in EMC 
requirement EN 61326-1:2006 electrical equipment 
for measurement, control and laboratory use.

Consult the factory for the most current information 
on products that have been CE certified. 

Figure 5.

 Dimensions of the TIY in DIN Housing

35mm

(1.37 in)

80mm

(3.15 in)

+IN

–IN

+PS –PS

38mm

129mm

(5.07 in)

CL

133mm

(5.27 in)

 138mm

(5.44 in)

(1.5 in)

ZERO

SPAN

SAVE

CANCEL

TIY

42mm

(1.65 in)

Содержание TIY

Страница 1: ...TIY TIY Programmable Isolated Thermocouple Transmitter May 2016 140 715 00G Programmable Isolated Thermocouple Transmitter...

Страница 2: ...ration 7 Setting the Configuration Jumpers 8 Calculating the TIY s Accuracy 10 LCD Readings 11 Standard and Quick Ranging 11 Standard Ranging 12 Quick Ranging 14 Installation 17 Mounting the TIY 17 HP...

Страница 3: ...couples types J K E T R S or N or a millivolt source and produces proportional 4 20 mA output Front panel push buttons set zero and span full scale values These values remain until they are changed b...

Страница 4: ...ding to SAMA Standard PMC 33 1 protection rates DIN and HP FL Housings 10V m ABC2 0 1 of maximum span for 30V m protection on DIN housing see the RF option 2LG and 2LS HP housing in explosion proof en...

Страница 5: ...ied ND No display indicator not provided NL Configured to provide output linear with input rather than linear with temperature jumper selectable RF DIN housing rates 30v m ABC 0 01 of maximum span whe...

Страница 6: ...0 21 F 0 60 C 1 08 F 0 50 C 0 90 F 0 40 C 0 72 F 0 15 C 0 27 F 0 08 C 0 14 F Output3 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of sp...

Страница 7: ...ed to ensure that the unit has not sustained any damage during transit and to set zero and span for your application Every unit should be Checked to verify that the appropriate TIY model has been orde...

Страница 8: ...echnician s bench or a similar lab type environment Setting the Configuration Jumpers Solderless jumpers are used to configure the TIY s user selectable operating features Figure 1 shows the layout of...

Страница 9: ...ORED INSTALLED INSTALLED INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED STORED J309 INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED INSTALLED STORED INSTALLED INSTALLED STORED INS...

Страница 10: ...s not temperature and the LCD readings are no longer valid J305 Ranging Method Calibration Stored Standard Ranging Installed Quick Ranging Standard Ranging requires an input source an output monitorin...

Страница 11: ...mocouple Range Input Codes Input Code J1 J2 J3 K1 K2 E1 E2 E3 T1 T2 T3 R1 S1 N1 N2 B1 Narrow Input Span 0 15 38 75 C 68 135 F 100 200 C 180 360 F 25 50 C 45 90 F 50 100 C 90 180 F 125 250 C 225 450 F...

Страница 12: ...with an LCD the user should disregard the LCD readings and respond only to the readings of the calibration equipment Storing jumper J305 configures the TIY for standard ranging See Figure 1 Figure 2...

Страница 13: ...e calibrating 5 Set input to the zero temperature value for the configured TIY range or to the millivolt equivalent as derived from standard thermocouple tables 6 Simultaneously press both ZERO push b...

Страница 14: ...TIY output 16 Disconnect calibration equipment If you used a millivolt source to calibrate the unit remove store jumper J301 enable RJC before placing the calibrated unit into service If you will need...

Страница 15: ...imultaneously the TIY is configured for Standard Ranging Check J305 See Figure 1 and Table 3 5 Set zero shown on LCD to desired setting using the Up or Down ZERO push button to increment or decrement...

Страница 16: ...input value 10 Press either ZERO push button to verify the zero setting Note If the zero input value is incremented too close to the full scale input setting the full scale setting will automatically...

Страница 17: ...units hold the unit in place when mounted in explosion proof enclosures The spring clips are squeezed inward to allow for positioning of the unit in the base of the explosion proof enclosure When rel...

Страница 18: ...elding the shield should be run all the way from the signal source to the receiving device see Note below The maximum length of un shielded input and output signal wiring should be 2 inches Note Some...

Страница 19: ...ions Figure 6 Installing the TIY The LCD During normal operation the LCD typically displays the applied input value As the input changes the readout of the LCD changes accordingly The LCD also display...

Страница 20: ...f any Moore Industries product fails to perform up to rated specifications call us for help Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide t...

Страница 21: ...allation diagram for the TIY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications This diagram must be used to augm...

Страница 22: ...DIES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EV...

Отзывы: