background image

14   The Interface Solution Experts

Programmable Isolated 
Thermocouple Transmitter

TIY

11.  Verify that the milliammeter or DC voltmeter 

indicates 4 mA (1 Vdc when using voltmeter 
and resistor).  This indicates that span was 
captured successfully.  Repeat steps 11 and 
12 until the reading is 4 mA.

12.  To trim zero-percent output, press one of the 

ZERO push buttons until the desired output 
level is indicated on the meter.  To set span, 
continue procedure.  Otherwise, go to step 
14.

13.  To trim span, press either SPAN push button 

until the desired output level is indicated on 
the meter.

14.  When desired values are captured and 

outputs trimmed, press both Up arrows 

simultaneously to save the new setting.

Note

:

 

The settings entered during calibration 

are retained until a subsequent calibration 

(quick or standard ranging) is performed.  
If the latest settings are not saved before 

removing power, or if the CANCEL push 

buttons are pressed simultaneously, the unit 

will revert to the last saved values.

15.  Check zero and full-scale settings by 

inputting zero and full scale, and monitoring 
the effect on TIY output.

16.  Disconnect calibration equipment.  If you 

used a millivolt source to calibrate the 
unit, remove (store) jumper J301 (enable 
RJC) before placing the calibrated unit into 
service.  If you will need to perform any 
subsequent quick ranging, install J305 (units 
with -ND option (no display) cannot be quick 
ranged).

Quick Ranging

Quick Ranging allows the user to calibrate the 
standard TIY without an input source or output 
monitoring device.  

After installing J305 (see Figure 1), a 12-42 Vdc 
power source applied to the +PS and –PS terminals 
of the TIY is all that is required to perform Quick 
Ranging.  The push buttons are used to set zero and 
span values.  The user-selected values are displayed 
on the unit’s LCD.

When quick ranging is selected, the TIY ignores 
signals to the input terminals (+IN and –IN).  The 
zero-percent output will be 4 mA for whatever value 
zero is set to with the ZERO push buttons, and the 
100-percent output will be 20 mA for whatever the 
full-scale value is set to with the SPAN push buttons.

Figure 3 illustrates the DC power hookup required to 
perform quick ranging of the TIY.

Note

:

 

Jumper J305 must be INSTALLED to 

perform quick ranging.  Verify its setting, 

along with other configuration jumpers, 

before beginning this procedure  

(See Figure 1 and Table 3).

SPAN

SAVE

ZERO

Содержание TIY

Страница 1: ...TIY TIY Programmable Isolated Thermocouple Transmitter May 2016 140 715 00G Programmable Isolated Thermocouple Transmitter...

Страница 2: ...ration 7 Setting the Configuration Jumpers 8 Calculating the TIY s Accuracy 10 LCD Readings 11 Standard and Quick Ranging 11 Standard Ranging 12 Quick Ranging 14 Installation 17 Mounting the TIY 17 HP...

Страница 3: ...couples types J K E T R S or N or a millivolt source and produces proportional 4 20 mA output Front panel push buttons set zero and span full scale values These values remain until they are changed b...

Страница 4: ...ding to SAMA Standard PMC 33 1 protection rates DIN and HP FL Housings 10V m ABC2 0 1 of maximum span for 30V m protection on DIN housing see the RF option 2LG and 2LS HP housing in explosion proof en...

Страница 5: ...ied ND No display indicator not provided NL Configured to provide output linear with input rather than linear with temperature jumper selectable RF DIN housing rates 30v m ABC 0 01 of maximum span whe...

Страница 6: ...0 21 F 0 60 C 1 08 F 0 50 C 0 90 F 0 40 C 0 72 F 0 15 C 0 27 F 0 08 C 0 14 F Output3 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of sp...

Страница 7: ...ed to ensure that the unit has not sustained any damage during transit and to set zero and span for your application Every unit should be Checked to verify that the appropriate TIY model has been orde...

Страница 8: ...echnician s bench or a similar lab type environment Setting the Configuration Jumpers Solderless jumpers are used to configure the TIY s user selectable operating features Figure 1 shows the layout of...

Страница 9: ...ORED INSTALLED INSTALLED INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED STORED J309 INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED INSTALLED STORED INSTALLED INSTALLED STORED INS...

Страница 10: ...s not temperature and the LCD readings are no longer valid J305 Ranging Method Calibration Stored Standard Ranging Installed Quick Ranging Standard Ranging requires an input source an output monitorin...

Страница 11: ...mocouple Range Input Codes Input Code J1 J2 J3 K1 K2 E1 E2 E3 T1 T2 T3 R1 S1 N1 N2 B1 Narrow Input Span 0 15 38 75 C 68 135 F 100 200 C 180 360 F 25 50 C 45 90 F 50 100 C 90 180 F 125 250 C 225 450 F...

Страница 12: ...with an LCD the user should disregard the LCD readings and respond only to the readings of the calibration equipment Storing jumper J305 configures the TIY for standard ranging See Figure 1 Figure 2...

Страница 13: ...e calibrating 5 Set input to the zero temperature value for the configured TIY range or to the millivolt equivalent as derived from standard thermocouple tables 6 Simultaneously press both ZERO push b...

Страница 14: ...TIY output 16 Disconnect calibration equipment If you used a millivolt source to calibrate the unit remove store jumper J301 enable RJC before placing the calibrated unit into service If you will need...

Страница 15: ...imultaneously the TIY is configured for Standard Ranging Check J305 See Figure 1 and Table 3 5 Set zero shown on LCD to desired setting using the Up or Down ZERO push button to increment or decrement...

Страница 16: ...input value 10 Press either ZERO push button to verify the zero setting Note If the zero input value is incremented too close to the full scale input setting the full scale setting will automatically...

Страница 17: ...units hold the unit in place when mounted in explosion proof enclosures The spring clips are squeezed inward to allow for positioning of the unit in the base of the explosion proof enclosure When rel...

Страница 18: ...elding the shield should be run all the way from the signal source to the receiving device see Note below The maximum length of un shielded input and output signal wiring should be 2 inches Note Some...

Страница 19: ...ions Figure 6 Installing the TIY The LCD During normal operation the LCD typically displays the applied input value As the input changes the readout of the LCD changes accordingly The LCD also display...

Страница 20: ...f any Moore Industries product fails to perform up to rated specifications call us for help Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide t...

Страница 21: ...allation diagram for the TIY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications This diagram must be used to augm...

Страница 22: ...DIES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EV...

Отзывы: