background image

TIY

The Interface Solution Experts   13

Programmable Isolated 

Thermocouple Transmitter

To monitor the output, either a milliammeter or a 
DC voltmeter with precision load resistor may be 
used.  If the voltmeter and load resistor are chosen, 
the voltmeter readings will be 1-5 Vdc representing  
4-20 mA.  Output current reading calculations can 
be made with the following formula:  V (voltage read-
ing)/250 ohms = mA

Note:

 

Jumper J305 must be STORED to perform 

Standard Ranging.  Verify its setting, along 

with other configuration jumpers, before 

beginning this procedure.

Standard Ranging the TIY

1.  Set Range and Gain/Offset Jumpers for the 

input type (See Table 4).

2.  Connect the TIY as shown in Figure 2.  

3.  To view the current zero setting, press and 

hold either ZERO push button. 

4.  To calibrate zero, press both ZERO push 

buttons simultaneously. 

 

 

 

 

 

 

Note:

 

In Standard Ranging, the LCD will 

continually flash while calibrating.

5.  Set input to the zero temperature value 

for the configured TIY range (or to the 
millivolt equivalent as derived from standard 
thermocouple tables). 

6.  Simultaneously press both ZERO push 

buttons twice.  This “captures” the applied 
zero input.

 

 

 

 

 

 

Note:

 

If the input value being captured exceeds 

the upper or lower programmed table limits 

for a particular input type (refer to Tables 1 

and 2), the LCD will flash -HI- or -LO-.  The 

input value must be within programmed 

table limits to be displayed or captured.

7.  Verify that the milliammeter or DC voltmeter 

reads 20 mA (5 Vdc when using voltmeter 
and load resistor).  This indicates that the 
zero value was captured successfully.  
Repeat steps 5-7 until the reading is 20 mA.

8.  To view current span value, press and hold 

either SPAN button. 

9.  To calibrate span, press both SPAN buttons 

simultaneously.

10.  Set input to the full scale temperature input 

for the configured TIY range (or to the 
millivolt equivalent as derived from standard 
thermocouple tables).  Press both SPAN 
buttons simultaneously twice to “capture” 
span.

ZERO

ZERO

ZERO

SPAN

SPAN

SPAN

Содержание TIY

Страница 1: ...TIY TIY Programmable Isolated Thermocouple Transmitter May 2016 140 715 00G Programmable Isolated Thermocouple Transmitter...

Страница 2: ...ration 7 Setting the Configuration Jumpers 8 Calculating the TIY s Accuracy 10 LCD Readings 11 Standard and Quick Ranging 11 Standard Ranging 12 Quick Ranging 14 Installation 17 Mounting the TIY 17 HP...

Страница 3: ...couples types J K E T R S or N or a millivolt source and produces proportional 4 20 mA output Front panel push buttons set zero and span full scale values These values remain until they are changed b...

Страница 4: ...ding to SAMA Standard PMC 33 1 protection rates DIN and HP FL Housings 10V m ABC2 0 1 of maximum span for 30V m protection on DIN housing see the RF option 2LG and 2LS HP housing in explosion proof en...

Страница 5: ...ied ND No display indicator not provided NL Configured to provide output linear with input rather than linear with temperature jumper selectable RF DIN housing rates 30v m ABC 0 01 of maximum span whe...

Страница 6: ...0 21 F 0 60 C 1 08 F 0 50 C 0 90 F 0 40 C 0 72 F 0 15 C 0 27 F 0 08 C 0 14 F Output3 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of sp...

Страница 7: ...ed to ensure that the unit has not sustained any damage during transit and to set zero and span for your application Every unit should be Checked to verify that the appropriate TIY model has been orde...

Страница 8: ...echnician s bench or a similar lab type environment Setting the Configuration Jumpers Solderless jumpers are used to configure the TIY s user selectable operating features Figure 1 shows the layout of...

Страница 9: ...ORED INSTALLED INSTALLED INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED STORED J309 INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED INSTALLED STORED INSTALLED INSTALLED STORED INS...

Страница 10: ...s not temperature and the LCD readings are no longer valid J305 Ranging Method Calibration Stored Standard Ranging Installed Quick Ranging Standard Ranging requires an input source an output monitorin...

Страница 11: ...mocouple Range Input Codes Input Code J1 J2 J3 K1 K2 E1 E2 E3 T1 T2 T3 R1 S1 N1 N2 B1 Narrow Input Span 0 15 38 75 C 68 135 F 100 200 C 180 360 F 25 50 C 45 90 F 50 100 C 90 180 F 125 250 C 225 450 F...

Страница 12: ...with an LCD the user should disregard the LCD readings and respond only to the readings of the calibration equipment Storing jumper J305 configures the TIY for standard ranging See Figure 1 Figure 2...

Страница 13: ...e calibrating 5 Set input to the zero temperature value for the configured TIY range or to the millivolt equivalent as derived from standard thermocouple tables 6 Simultaneously press both ZERO push b...

Страница 14: ...TIY output 16 Disconnect calibration equipment If you used a millivolt source to calibrate the unit remove store jumper J301 enable RJC before placing the calibrated unit into service If you will need...

Страница 15: ...imultaneously the TIY is configured for Standard Ranging Check J305 See Figure 1 and Table 3 5 Set zero shown on LCD to desired setting using the Up or Down ZERO push button to increment or decrement...

Страница 16: ...input value 10 Press either ZERO push button to verify the zero setting Note If the zero input value is incremented too close to the full scale input setting the full scale setting will automatically...

Страница 17: ...units hold the unit in place when mounted in explosion proof enclosures The spring clips are squeezed inward to allow for positioning of the unit in the base of the explosion proof enclosure When rel...

Страница 18: ...elding the shield should be run all the way from the signal source to the receiving device see Note below The maximum length of un shielded input and output signal wiring should be 2 inches Note Some...

Страница 19: ...ions Figure 6 Installing the TIY The LCD During normal operation the LCD typically displays the applied input value As the input changes the readout of the LCD changes accordingly The LCD also display...

Страница 20: ...f any Moore Industries product fails to perform up to rated specifications call us for help Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide t...

Страница 21: ...allation diagram for the TIY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications This diagram must be used to augm...

Страница 22: ...DIES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EV...

Отзывы: