background image

10   The Interface Solution Experts

Programmable Isolated 
Thermocouple Transmitter

TIY

The configuration jumpers set the following features:

J301

 – Reference Junction Compensation (RJC)

  Stored – RJC Activated 

Installed – RJC Inactive 
This jumper is valid for thermocouple 
inputs.   

 

When J301 is installed (No 

RJC), the TIY assumes the reference junction to 
be at zero degrees Celsius (32°F), and allows 
standard ranging to be accomplished using a 
millivolt input source and copper wire instead of 
thermocouple wire.

J302

 – Displayed Temperature Type

  Stored – Temperature displayed in Fahrenheit 

Installed – Temperature displayed in Celsius 
If a millivolt range is selected with the Range 
Jumpers, the LCD displays millivolts and this 
jumper has no effect

J303

 – Burnout

  Stored – Upscale Burnout

 

Installed – Downscale Burnout 
This jumper determines the reaction of the TIY 
output when an error is detected or when the 
input is open.  The output will normally follow the 
burnout jumper setting.

J304

 – Linearization

  Stored – Linearization 

Installed – No Linearization 
This jumper is valid for thermocouple inputs 
ONLY.  When J304 is installed (no linearization), 
the output is linear with input millivolts, not 
temperature, and the LCD readings are no 
longer valid.

J305

 – Ranging Method (Calibration)

  Stored – Standard Ranging 

Installed – Quick Ranging 
Standard Ranging requires an input source, an 
output monitoring device, and power to perform 
ranging.  The push buttons are used to capture 
the zero and span inputs and trim the zero and 
full-scale outputs.

Quick Ranging can only be performed on units with 
LCDs.  To set the 4-20 mA output with this ranging 
method, only power is needed for the unit.  The push 
buttons are used to enter values for zero and span 
(full-scale).

Note

:

 

Any time a jumper is changed while power 

is applied, one of the four push buttons 

must be pressed for the TIY to acknowledge 

the configuration change. 

Calculating the TIY’s Accuracy

The output accuracy of the TIY is ±0.05% of span.  
Accuracy improves for wider spans, and degrades for 
narrower spans.

Table 5 shows selected narrow, medium, and wide 
spans for each programmed input code (by thermo-
couple type).  At the top of each column is the accu-
racy rating for the spans listed in that column. 

The accuracy formula shown below is used for cal-
culating the total error for a TIY programmed for the 
J1 input code (see Table 1) with a wide input span of 
300°C (see Table 5). 

 

EXAMPLE:

Input Ac (Span x Output Accuracy) + Cold 
Junction Compensation Accuracy = Total Error (in 
degrees)

±0.08°C + ±(300°C x 0.05%)°C + ±0.25°C = ±0.48°C

Содержание TIY

Страница 1: ...TIY TIY Programmable Isolated Thermocouple Transmitter May 2016 140 715 00G Programmable Isolated Thermocouple Transmitter...

Страница 2: ...ration 7 Setting the Configuration Jumpers 8 Calculating the TIY s Accuracy 10 LCD Readings 11 Standard and Quick Ranging 11 Standard Ranging 12 Quick Ranging 14 Installation 17 Mounting the TIY 17 HP...

Страница 3: ...couples types J K E T R S or N or a millivolt source and produces proportional 4 20 mA output Front panel push buttons set zero and span full scale values These values remain until they are changed b...

Страница 4: ...ding to SAMA Standard PMC 33 1 protection rates DIN and HP FL Housings 10V m ABC2 0 1 of maximum span for 30V m protection on DIN housing see the RF option 2LG and 2LS HP housing in explosion proof en...

Страница 5: ...ied ND No display indicator not provided NL Configured to provide output linear with input rather than linear with temperature jumper selectable RF DIN housing rates 30v m ABC 0 01 of maximum span whe...

Страница 6: ...0 21 F 0 60 C 1 08 F 0 50 C 0 90 F 0 40 C 0 72 F 0 15 C 0 27 F 0 08 C 0 14 F Output3 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of sp...

Страница 7: ...ed to ensure that the unit has not sustained any damage during transit and to set zero and span for your application Every unit should be Checked to verify that the appropriate TIY model has been orde...

Страница 8: ...echnician s bench or a similar lab type environment Setting the Configuration Jumpers Solderless jumpers are used to configure the TIY s user selectable operating features Figure 1 shows the layout of...

Страница 9: ...ORED INSTALLED INSTALLED INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED STORED J309 INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED INSTALLED STORED INSTALLED INSTALLED STORED INS...

Страница 10: ...s not temperature and the LCD readings are no longer valid J305 Ranging Method Calibration Stored Standard Ranging Installed Quick Ranging Standard Ranging requires an input source an output monitorin...

Страница 11: ...mocouple Range Input Codes Input Code J1 J2 J3 K1 K2 E1 E2 E3 T1 T2 T3 R1 S1 N1 N2 B1 Narrow Input Span 0 15 38 75 C 68 135 F 100 200 C 180 360 F 25 50 C 45 90 F 50 100 C 90 180 F 125 250 C 225 450 F...

Страница 12: ...with an LCD the user should disregard the LCD readings and respond only to the readings of the calibration equipment Storing jumper J305 configures the TIY for standard ranging See Figure 1 Figure 2...

Страница 13: ...e calibrating 5 Set input to the zero temperature value for the configured TIY range or to the millivolt equivalent as derived from standard thermocouple tables 6 Simultaneously press both ZERO push b...

Страница 14: ...TIY output 16 Disconnect calibration equipment If you used a millivolt source to calibrate the unit remove store jumper J301 enable RJC before placing the calibrated unit into service If you will need...

Страница 15: ...imultaneously the TIY is configured for Standard Ranging Check J305 See Figure 1 and Table 3 5 Set zero shown on LCD to desired setting using the Up or Down ZERO push button to increment or decrement...

Страница 16: ...input value 10 Press either ZERO push button to verify the zero setting Note If the zero input value is incremented too close to the full scale input setting the full scale setting will automatically...

Страница 17: ...units hold the unit in place when mounted in explosion proof enclosures The spring clips are squeezed inward to allow for positioning of the unit in the base of the explosion proof enclosure When rel...

Страница 18: ...elding the shield should be run all the way from the signal source to the receiving device see Note below The maximum length of un shielded input and output signal wiring should be 2 inches Note Some...

Страница 19: ...ions Figure 6 Installing the TIY The LCD During normal operation the LCD typically displays the applied input value As the input changes the readout of the LCD changes accordingly The LCD also display...

Страница 20: ...f any Moore Industries product fails to perform up to rated specifications call us for help Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide t...

Страница 21: ...allation diagram for the TIY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications This diagram must be used to augm...

Страница 22: ...DIES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EV...

Отзывы: