The Interface Solution Experts

19

THZ & TDZ

Operation

Once programmed, calibrated, installed, and supplied
with the correct power, THZ and TDZ transmitters
begin to operate immediately.  Depending upon envi-
ronmental conditions, they can be expected to operate
unattended for extended periods of time.

HART Protocol

This section of the manual gives an overview of the
HART format used by THZ and TDZ modules during
operation.  Use the information in this section to pro-
cess the data provided by the module(s) during opera-
tion.  For more information on the HART protocol,
contact the HART Foundation at:

The HART Communication Foundation
9390 Research Blvd, Suite 1-350
Austin, TX 78759-6540 U.S.A.
(512) 794-0369
www.ccsi.com/hart

Device Types

To implement two-way communication between the
THZ and the device being used to configure it or re-
ceive its information, the THZ or TDZ operates in a
HART Master/Slave structure.  The THZ or TDZ is the
Slave (or slaves in a multidrop network).

There can be two Masters per system:  a Primary
Master and a Secondary Master.  Masters are typically
either a HART Hand-Held Communicator or a HART-
based control system.

In many applications, the Primary Master is a HART
Hand-Held Communicator.  The communicator is
used solely as a configuration tool to set up the
transmitter, periodically view its real-time process
measurement, or view its operating and diagnostic
information from a loop termination point.

Digital Signal

One of the advantages of the HART protocol is that
the digital information is conveyed by the same wires
used to output the 4-20mA signal.  After being polled
by the master, the THZ or TDZ responds to the inquiry
by modulating the 4-20mA current 0.5 mA above or
below the output signal.  1200 Hz represents 1 and
2200 Hz represents 0.

Communication Speed and Format

The speed of the HART transmission is 1200 baud.
The time delay between a master initiating a request
for data from a slave and the slave receiving and ac-
knowledging the request depends upon which com-
mand is issued.  Generally, a master can poll a slave
2-3 times per second.

The byte structure of the HART signal is:

1 Start Bit, 8 Data Bits, 1 Odd Parity Bit, 1 Stop Bit.

Maintenance

Moore Industries suggests a quick check for terminal
tightness and general unit condition every 6-8 months.
Always adhere to any site requirements for pro-
grammed maintenance.

Customer Support

Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services.  We perform a battery of stringent qual-
ity assurance checks on every unit we ship.  If any
Moore Industries product fails to perform up to rated
specifications, call us for help.  Our highly skilled staff
of trained technicians and engineers pride themselves
on their ability to provide timely, accurate, and practi-
cal answers to your process instrumentation ques-
tions.

Factory phone numbers are listed on the back cover of
this manual.

If problems involve a particular THZ or TDZ, there
are several pieces of information that can be gath-
ered 

 before you call the factory that will help our

staff get the answers you need 

in the shortest time

possible.  For the fastest service, gather the com-
plete model and serial number(s) of the problem
unit(s) and the job number of the original sale.

Содержание TDZ

Страница 1: ...Z TDZ THZ TDZ Smart HART Temperature Transmitters Displays April 2016 235 745 00 F Smart HART Temperature Transmitters Displays All product names are registered trademarks of their respective companie...

Страница 2: ...des all the tables and illustrations you will need to easily setup your unit from startup to hookup Reference the HelpMap if you are looking for more detailed information than is provided in this manu...

Страница 3: ...ftware 10 Connecting the THZ or TDZ to the PC 10 Necessary Equipment Table 10 Using the PC Configuration Program 11 Using the HART Communicator 13 Programming when a Device Description is Available 13...

Страница 4: ......

Страница 5: ...make them the ideal solution when measurements must be made in remote or otherwise difficult to ac cess locations Model and Serial Numbers Moore Industries uses a system of model and serial numbers to...

Страница 6: ...ree wire connections 35 wire 10 copper sensor 5 SensorLeadResistance Effect 1 0 in reading of lead resistance for 2 wire sensors 1 0 in reading of lead of unbalanced resistance for 3 wire sensors no e...

Страница 7: ...346 to 1418 F 270 to 1390 C 454 to 2534 F 270 to 1013 C 454 to 1855 4 F 270 to 407 C 454 to 764 6 F 50 to 1786 C 58 to 3246 8 F 50 to 1786 C 58 to 3246 8 F 200 to 1836 C 392 to 3336 8 F 270 to 1316 C...

Страница 8: ...xplosion Proof LH2 head with two entry ports inch NPT conduit and process black metal cover LH2MS Explosion Proof LH2 head with two entry ports M20 cable and inch NPT process black metal cover CH6 Pol...

Страница 9: ...16mA 0 004 of span 16mA 0 004 of span 16mA TDZ HP THZ DIN THZ HPP Ambient Temperature Effects Sensor Type RTD T C Millivolt Ohm Digital Accuracy per 1 C 1 8 F change in Ambient 0 0015 C 0 0015 C 0 000...

Страница 10: ...n 49mm 1 92 in 27mm 1 05 in 4 X 40 0 125 in depth 2 PLACES 33mm 1 3 in L C 33mm 1 3 in Figure 3 THZ Hockey Puck HPP Housing Dimensions FRONT VIEW SIDE VIEW 61mm 2 40 in PS PS 1 2 3 4 TDZ 83mm 3 27 in...

Страница 11: ...with the THZ HPP 92mm 3 62 in 9mm 0 35 in 87mm 3 43 in Conduit Entry Port 89mm 3 5 in 84mm 3 31 in C L 61mm 2 40 in 2 in Pipe Bracket Mounting Holes 4 61mm 2 40 in Process Connection 1 2 in NPT N and...

Страница 12: ...END OF THE THZ DH PROVIDE EASY ACCESS TO THE DISPLAY FRONT OR THE CONDUIT CONNECTIONS BACK DISPLAY GLASS COVER CONNECTIONS METAL COVER 0 100 102mm 4 02 in 154mm 6 06 in 70mm 2 76 in 124mm 4 88 in 90mm...

Страница 13: ...a Configuration File and stored in the instruments memory You can save a backup copy of the file on your PC hard drive or disk The transmitter communicates with the PC through a HART modem connection...

Страница 14: ...2 3 or 4 set to 4800 baud no parity 8 data bits and 1 stop bit Moore Industries part number 803 048 26 or equivalent Version 1 0 or greater successfully installed to the hard drive Fisher Rosemount M...

Страница 15: ...ll display properties of the transmitter 3 Input Configuration Use this section to select and configure the sensor type Choose from Thermo couple RTD Millivolt Resistance or Potentiometer 4 Variables...

Страница 16: ...ESISTANCE BOX CURRENT METER THERMOCOUPLE SIMULATOR 3 WIRE RTD OR DECADE RESISTANCE BOX MILLIVOLT INPUT 4 WIRE RTD OR DECADE RESISTANCE BOX POTENTIOMETER INPUT HART MODEM CONNECTS TO SERIAL COM PORT OF...

Страница 17: ...ore Industries can factory configure parameters that are not accessible through the generic DD Moore Industries can update your HART Communi cator with all of the latest approved HART Device Descripti...

Страница 18: ...OG OUT ZERO FULL 2 OUTPUT TRIM PROCEED CHANGE HART OUTPUT 1 POLL ADDR 2 BURST MODE 3 BURST OPTION CONFIGURE DEV INFO 1 TAG 2 DESCRIPTOR 3 MESSAGE 4 DATE 5 FINAL ASSY 6 DEVICE ID 7 H W REVISION CONFIGU...

Страница 19: ...tag 8 characters date descriptor i e a location code of up to 16 characters a message 32 charac ters and final assembly numbers for the transmit ter You cannot change the device ID or the Hardware Rev...

Страница 20: ...USL DEVICE INFORMATION 1 DISTRIBUTOR 2 MODEL 3 DEV ID 4 TAG 5 DATE SENSORS 1 PV 2 PV SNSR 3 SENSOR INFORMATION SIGNAL CONDITION 1 SNSR DAMP 2 URV 3 AI LRV 4 AI XFER FNCTN 5 AI RANGE OUTPUT CONDITION 1...

Страница 21: ...menu allows you to enter a name for an individual transmitter the units of measurement the upper and lower range and sensor values and a damping time between 0 and 30 seconds Damping smooths input fl...

Страница 22: ...from or transmit configuration information to the transmitter from any where along the HART digital link Make sure that the total loop resistance is at least 250 so that the 4 20mA signal containing...

Страница 23: ...ires used to output the 4 20mA signal After being polled by the master the THZ or TDZ responds to the inquiry by modulating the 4 20mA current 0 5 mA above or below the output signal 1200 Hz represent...

Страница 24: ...3 0 or earlier First verify that you have a copy of Internet Ex plorer then check the version by going to the Help and About Internet Explorer menu in Internet Ex plorer program If you have an older...

Страница 25: ...which is unspecified except that it must not be supplied from or contain under normal or abnormal conditions a source of potential with respect to earth in excess of 250 VRMS or 250 VDC which is cons...

Страница 26: ...red to be the Safe Area s maximum voltage 2 The Barrier or other Associated Apparatus must be approved by the specific CSA EECS FM LCIE SAA SIRA TUV etc certifying agency for I S connections in Class...

Страница 27: ...er or other Associated Apparatus must be approved by the specific CSA EECS FM LCIE SAA SIRA TUV etc certifying agency for I S connections in Class I III Division 1 Groups A G or equivalent Zone classi...

Страница 28: ...24 The Interface Solution Experts THZ TDZ...

Страница 29: ...ers A switch or circuit breaker must be wired in series with the AC power conductors The switch or cir cuit breaker used must be located within three meters of the unit WARNING Terminals on this unit...

Страница 30: ...R BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT B...

Страница 31: ...injury or other harm due to contact b does not produce excessive surface temperature infra red electromagnetic ionizing radiation and c have no non electrical dangers CAUTION Read understand and adhe...

Страница 32: ...s specifications or area classifications meet the operational or safety requirements for the installation consult Moore Industries prior to installation Installation of LH Enclosure Apparatus 1 Insta...

Отзывы: