SPA
20
The Interface Solution Experts
Site-Programmable RTD &
Thermocouple Limit Alarm Trips
SET HI/LO
23. From the “SET HILO” screen, press
SELECT.
24. Use the arrow buttons to toggle the alarm
function between high alarm operation
(trips when input exceeds the trip point
setting) and low alarm operation (trips
when input drops below the trip point).
25. Press SELECT when the display shows
the desired setting. This returns the unit
to the Alarm Configuration menu at “SET
LAT” (choose latching or non-latching
alarm function).
26. Press SELECT to access the latch/no
latch setting screen, or use the arrow
buttons to scroll through the other alarm
operating parameters. Press SELECT to
access the screen(s) for the parameters
displayed, or scroll to “EXIT ALRM” and
press SELECT to access the menus for
another alarm (if installed), or to return to
the Main Menu.
NOTE:
An alarm’s HI/LO setting can affect the way
the SPA functions on sensor failure
(when equipped with the –SF3 option).
Refer to the Operation section under
“Sensor Failure and Alarms”
for more information.
SET LATCHING/NON-LATCHING
27. From the “SET LAT” screen, press
SELECT.
28. Use the arrow buttons to toggle the
alarm function between latching (alarm
stays tripped until input returns to normal
(allowing for any deadband) AND unit is
manually reset) and non-latching (alarm
returns to normal as soon as input returns
to normal, allowing for any deadband)
function.
29. Press SELECT when the display shows
the desired setting. This returns the unit
to the Alarm Configuration menu at “EXIT
ALRM”.
30. Press SELECT to bring up the menu for
the next installed alarm. If no additional
alarms are installed, or to return to the
Main Menu, press SELECT from “EXIT
ALRM”.
To set the operating parameters for the
next installed alarm, use the arrow buttons
from the “EXIT ALRM” screen to display
the next alarm, “AL2 CONF”, for example,
and press SELECT, and return to step 3.
When all of the alarm parameters for all
of the installed alarms have been set
as desired, press SELECT from “EXIT
ALRM”, and press SELECT again from
“ALRM EXIT”. This returns the unit to the
Main Menu at “PASS WORD”