13

SPA

Site-Programmable  RTD & 

Thermocouple Limit Alarm Trips

 

Use the arrow buttons to toggle the 
display, turning RJC ON or OFF, and press 
SELECT.

5.  Skip to step 10.

6.  If an RTD was selected in step 3, the next 

screen displayed may offer selections for a 
resistance range, “XXXX OHMS”. 
 
If a direct ohms source (

) was selected 

as sensor type, skip to step 7. 
 
Note that some RTD selections (from 
step 3) automatically default to a standard 
range, and where this occurs, the next 
screen displayed will be the selection of 
the wiring configuration to be used, “# OF 
WIRES”.  If “# OF WIRES” is displayed 
after selecting sensor type in step 3, go 
directly to step 7.

 

From the “XXXX OHMS” screen, use 
the arrow buttons to scroll through the 
available ranges.  Choose the desired 
range by pressing SELECT, which brings 
up the “# OF WIRES” screen.

7.  From “# OF WIRES” use the arrow buttons 

to choose the type of RTD sensor to be 
used, or the number of RTD sensors to be 
used.  When the display shows the setup 
desired, press SELECT.

8.  If a single sensor (2-, 3-, or 4-wire) 

selection was made in step 7, skip to step 
10.

9.  If “DUAL 2W” or “DUAL 3W” was selected 

in step 7, the next display allows you to 
choose between differential or averaged 
inputs.  Use the arrow buttons to choose 
the desired setup and press SELECT.

10. The next display is the menu for 

the selection of functional options, 
”CONF OPTS”.  To skip the rest of the 
configuration menus and return to the 
display of the measured input value, press 
the up arrow button 2 times (to “CONF 
EXIT”), and press SELECT.

Configure Sensor

In the TPRG, if the security jumper is not installed 
(see Figure 2), the password sub-menu is bypassed, 
and the Configure Sensor menu is accessed when 
SELECT is pressed from the display of the measured 
input value.  Figure 7 shows the Configure Sensor 
menu.

The Configure Sensor menu sets:

•  RTD, TC or mV, or 

•  Range (for 

 or RTD)

•  # of input wires (for RTD or 

)

•  Reference Junction Compensation (RJC) enable/

disable, and dual sensor input differential or  
averaging

To configure the sensor of the TPRG SPA:

1.  Press SELECT from the “CONF SENS” 

display of the Main Menu (see Figure 5).

2.  Use the up or down arrow buttons to scroll 

through the options for sensor/inputs.  
There are several types of RTDs and 
Thermocouples, as well as direct millivolt 
source and resistance inputs available.

 

The default display for this menu is always 
the last setting.  For example, if a J-type 
thermocouple was selected as the sensor 
type last, “TC J” will be displayed when this 
menu is accessed.

3.  When the display shows the type of sensor 

to be used with the SPA, press SELECT.

4.  If an RTD or direct resistance source was 

selected in step 3, skip to step 6.

 

If a thermocouple or millivolt source 
was selected in step 3, the next screen 
will be the choice of reference junction 
compensation ON or OFF.

Содержание SPA TPRG

Страница 1: ...The Interface Solution Experts 1 SPA SPAApril 2016 224 721 00D Site Programmable RTD Thermocouple Limit Alarm Trips Site Programmable RTD Thermocouple Limit Alarm Trips TPRG...

Страница 2: ...y Jumper installed in OFF position Security Jumper installed in ON position VIEW current settings Front Panel Push Buttons Inactive during operation Inactive during operation SELECT Use or push button...

Страница 3: ...fications 5 Alarm Terminology 7 Internal Settings 8 Programming the TPRG SPA 10 Main Menu View Settings 10 Password 12 Configure Sensor 13 Configure Options 15 Configure Alarm s 17 Change the Security...

Страница 4: ...s two ways to set the alarm trip point If an input source is either unavailable or inconvenient the unit s front panel push buttons and integral liquid crystal display LCD can be used to enter the des...

Страница 5: ...resis repeatability and adjustment resolution Response Time 400ms maximum time for output to go from 10 to 90 for step change on input Ripple up to 120Hz Current output 10mV peak to peak max when meas...

Страница 6: ...00 C to 400 C 328 F to 752 F 0 C to 1760 C 32 F to 3200 F 0 C to 1760 C 32 F to 3200 F 130 C to 1300 C 202 F to 2372 F 400 C to 1820 C 752 F to 3308 F Accuracy 0 1 C 100 0 2 C 200 300 400 0 15 C 500 1...

Страница 7: ...call for a buffer zone or Deadband around the trip point to allow for minute fluctuations in the process input In the SPA the reset point is deter mined by the deadband setting Latching SPA alarms wi...

Страница 8: ...and the location of each of the controls for setting Password Security ON OFF Figure 2 Failsafe Non failsafe Alarm Function Figure 3 Current Source Sink or Voltage Figure 4 Available in AO equipped SP...

Страница 9: ...e Alarm Function NO1 CM1 NC1 NO2 CM2 NC2 GND RELAY 1 RELAY 2 POWER AC OR DC SLIDING PANEL SPA UNDERSIDE SET CURRENT SOURCE SINK OR VOLTAGE SOURCE CURRENT BACK FRONT SINK CURRENT VOLTAGE FAILSAFE NON F...

Страница 10: ...only Standard Ranged Zero and Full Scale AO AOZ equipped units only Analog Output Trim AO AOZ equipped units only Main Menu View Settings Figure 5 gives an overview of the first level of menus used to...

Страница 11: ...E SCREEN SHOWS PASS LOCK VIEW SELECT READ ONLY VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT READ BUT DO NOT CHANGE CURRENT SETTINGS CONF EXIT CONF SE...

Страница 12: ...settings can be viewed but not changed 4 If you have entered the correct password the Configure Sensor menu CONF SENS will be accessed If not the display will show a READ ONLY message 5 From READ ONL...

Страница 13: ...t display is the menu for the selection of functional options CONF OPTS To skip the rest of the configuration menus and return to the display of the measured input value press the up arrow button 2 ti...

Страница 14: ...STANCES VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT USE UP DOWN BUTTONS TO SCROLL THROUGH AVAILABLE WIRING USE UP DOWN BUTTONS TO TOGGLE BETWEEN RJC ON OR RJC OFF 3 WIRE RJ...

Страница 15: ...between a sensor failure and an alarm condition on the input and depending upon which of the available SPA options is installed the SET FAIL menu can be used to set the following operating parameters...

Страница 16: ...ENGU OPTS EXIT SET LIN DEG C LIN ON FAIL HIGH SET FAIL OPTS EXIT SET ENGU CONF ALRM MAIN MENU VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT USE BUTTO...

Страница 17: ...through 6 In the INP TRIP menu the SPA must be set up with calibration equipment see Figure 10 In this the Standard Ranging procedure the unit captures its trip point from the input of an adjustable s...

Страница 18: ...VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT ENTER TRIP POINT SMART RANGING IF NO OTHER ALARMS ARE INSTALLED GOES TO NEXT ALARM DISPLAYS ENGINEERING UNITS USE ARROW BUTTONS TO SET DISPLAY TO DESIRE...

Страница 19: ...ncrements 21 Press SELECT when the display shows the desired delay setting This returns the unit to the Alarm Configuration menu at SET HILO choose high or low alarm function 22 Press SELECT to access...

Страница 20: ...the SF3 option Refer to the Operation section under Sensor Failure and Alarms for more information SET LATCHING NON LATCHING 27 From the SET LAT screen press SELECT 28 Use the arrow buttons to toggle...

Страница 21: ...be locked out READ ONLY mode Figure 11 shows the menu 1 From the PASS WORD screen press SELECT to access PASS 2 Use the arrow buttons to increment or decrement the password number to be stored in unit...

Страница 22: ...LECT 3 Use the arrow buttons to raise or lower the value displayed according to the requirements of the application NOTE The engineering units displayed on this screen are determined by the setting en...

Страница 23: ...put level 4 Press SELECT storing the zero setting in SPA memory and accessing SAVE FULL 5 Press SELECT again The screen will flash the input level 6 Adjust input to the desired 100 level The screen wi...

Страница 24: ...s to choose the level zero or full scale that is to be trimmed 4 Press SELECT to begin the trim process The display will begin to flash the TRIM ZERO or TRIM FULL screen depending upon the option chos...

Страница 25: ...ly START TRIM OUT TRIM ZERO TRIM ZERO TRIM FULL TRIM FULL EXIT OUT CONF EXIT INP Z FS CONF EXIT EXIT OUT TRIM FULL TRIM ZERO EXIT OUT TRIM FULL TRIM ZERO VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELEC...

Страница 26: ...back panel over the top lip of the rail and pivot downward until the housing locks into place To mount the unit on G type rail seat the extrusion under the top lip of the rail and again pivot downward...

Страница 27: ...f Moore Industries instruments can be classified as receivers IPT 2 IPX 2 etc and some can be classified as transmitters TRX TRY etc while some are both a receiver and a transmitter SPA 2 HIM etc Henc...

Страница 28: ...3 AND 4 WIRE RTD HOOKUPS MULTIPLE RTD HOOKUPS FOR DIFFERENTIAL AND AVERAGED INPUTS SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 1 SENSOR 2 SENSOR 1 SENSOR 2 NOTE IN DIFFERENTIAL MEASUREMENT APPLICATIONS ALWAYS C...

Страница 29: ...B6 B7 B8 B9 Not Present Not Present NO3 NO3 NO2 CM3 CM3 CM2 NC3 NC3 NC2 NO2 CM2 NC2 Relay 1 above Relay 1 above NO4 CM4 NC4 Not Present NO2 CM2 NC2 Relay 2 above 1 Relay 1PRG 2 Relays 2PRG 3 Relays 3...

Страница 30: ...arm condition relative to the trip point setting A red LED indicates alarm NOTE The state of the SPA relays in alarm or non alarm is determined by the failsafe non failsafe setting of the unit s inter...

Страница 31: ...into unit memory This can be caused by power loss or fluctuation during power up Reference Junction Compensation Resistor Burnout Internal Table Error The linearization curve pro gramming is not corr...

Страница 32: ...THE SOLE AND EXCLUSIVE REM EDIES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRI...

Отзывы: