RP424PFC Indoor Gas Fireplace
Page 65
XG0781 - 151104
Maintenance
Step 17:
Remove screws securing the pilot cable cover.
Step 18:
Remove the pilot cable cover.
Figure 147.
Figure 148.
Step 19:
Unplug the pilot cable from the valve and pass the wire
through the access hole.
Figure 149.
Figure 150.
Step 20:
Remove the burner from the fireplace.
Figure 151.
Step 21:
Remove the pilot draft shield from the old burner.
Step 22:
Installation is the reverse of removal. Connect the pilot
cable, secure the burner, connect the gas flex line and pilot lines.
Step 23:
When the burner is secured in place but before installing
the light trays, the gas connections must be tested. Resupply power
and gas to the fireplace.
Step 24:
Light the fireplace and check connections under normal
operating pressure with a commercially available leak check solution.
Tighten any areas where bubbling occurs or a leak is detected.
DO NOT USE A FLAME OF ANY KIND TO TEST FOR LEAKS.
Step 25:
Turn the fireplace off and install the pilot draft shield that
was removed from the old burner. Reinstall the light trays. Test the
lights to ensure they are functional.
Step 26:
Reinstall the burner media tray mounting brackets, the
burner media tray, and the rail ends.
Step 27:
Reinstall the inner valve cover and access panel. See
Accessing the Valve
.
Step 28:
Reinstall the burner media. See
Section 9
for installation
of accessories.
Step 29:
Reinstall the glass barriers. See
Section 10
for installation
and removal of glass.
Figure 152.