RP424PFC Indoor Gas Fireplace
Page 61
XG0781 - 151104
Maintenance
Step 8:
Gently rotate the Pilot gas line up and away from the valve.
Lift the valve assembly away from the fireplace.
Figure 128.
Step 9:
Install the replacement valve.
Note:
Be sure to install the
replacement valve in the correct orientation. The electrical connections
align with the right side of the fireplace when installed correctly. See
Figure 130
.
Figure 129.
Right Side
Left Side
Figure 130.
Step 10:
Installation of the valve is the reverse of removal.
Figure 131.
Valve assembly installed.
Step 11:
Resupply power and gas to the fireplace.
Step 12:
Light the fireplace.
Step 13:
Check connections under normal operating pressure with a
commercially available leak check solution. Tighten any areas where
bubbling occurs or a leak is detected.
DO NOT USE A FLAME OF ANY KIND TO TEST FOR LEAKS.
Figure 132.
Step 11:
Turn the fireplace off and reinstall the inner valve cover and
access panel. See
Accessing the Valve
.
Step 12:
Reinstall the glass barriers. See
Section 10
for installation
and removal of glass.