HDV Series Direct Vent Gas Fireplace
0
56D3048
VeNtING INStAllAtIoN
•
The maximum number of 45° elbows permitted per side
wall installation is two (). These elbows can be installed
in either the vertical or horizontal run.
•
For each 45° elbow installed in the horizontal run, the
length of the horizontal run MUST be reduced by 18" (45
cm). This does not apply if the 45° elbows are installed
on the vertical part of the vent system.
•
The maximum number of elbow degrees in a system is
70°.
Figure 24
1
2
3
4
1
2
3
4
example:
Elbow 1 = 90°
Elbow = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation = 70°
Figure 24 -
Maximum Elbow Usage
1 + 2 + 3 + 4 = 270°
FP1180
VO584-100
Vent Opening
2/99 djt
Figure 25 -
Exterior Wall Framing Dimensions
10
Z\x
"
(67 mm)
10
Z\x
"
(67 mm)
Combustible Wall
Framing
VO584-100
8
Z\x
"
(16 mm)
Noncombustible Wall
HoRIZoNtAl WItH VeRtICAl RISe
(tHRouGH-tHe-WAll) APPlICAtIoNS
1. Locate and cut the vent opening in the wall. For com-
bustible walls first frame in opening.
Combustible Interior Walls:
Cut a 1
Z\x
"H x 10
Z\x
" W
hole through the interior wall.
Combustible exterior Walls:
Cut a 10
Z\x
"H x 10
Z\x
"W
square hole through the exterior wall frame.
Figure 25
Noncombustible Walls:
Hole opening should be 8
Z\x
"
(16mm) in diameter.
. The center of the hole should align with the center line
of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot.
Figure 25