HDV Series Direct Vent Gas Fireplace
FP2465
vent clearance
*3”
Min.
**1”
Min.
1”
Min.
*3”
Min.
**1”
Min.
1”
Min.
48
56M
”
(1226 mm)
34
6
”
(880 mm)
* A Minimum of 3" Clearance to the Top Is Required
Along Horizontal Length until Flue Pipe Penetrates
Outside Wall.
** A Minimum 1" Clearance to Combustibles Permitted
All Around Flue at Outside Wall.
FP465
Figure 10 -
Combustible Clearance to Venting Pipes
W
ARNING
this fireplace must be vented to the outside. the venting system must
NeVeR be attached to a chimney serving a separate solid fuel burning
appliance. each gas appliance must use a separate vent system. Do not
use common vent systems.
VeNtING INStAllAtIoN
W
ARNING
Horizontal sections of this vent system require a minimum of 3” clearances
to combustibles at the top of the flue and 1” clearance at the sides and
bottom until the flue penetrates the outside wall. A minimum 1” clearance
all around the flue is acceptable at this point of penetration. If vertical rise
is 7
Z\x
” feet or higher when top venting, the clearance to combustibles is
1” on all sides of the horizontal run.
Vertical sections of this vent system require a minimum of 1” clearance
to combustibles on all sides of the pipe.