HDV Series Direct Vent Gas Fireplace
14
56D3048
VeNtING INStAllAtIoN
INStAllAtIoN PlANNING
There are two basic types of direct-vent installation:
•
Horizontal Termination
•
Vertical Termination
It is important to select the proper length of vent pipe for
the type of termination you choose. It is also important to
note the wall thickness.
FoR HoRIZoNtAl teRMINAtIoN
Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every
1" of run towards the termination below 7
Z\x
feet of vertical rise. With 7
Z\x
feet or more vertical rise
off top of fireplace, the horizontal run may be level. NEVER run vent piping down.
You may use up to three 90° elbows in this vent configuration. Refer to
Horizontal Termination
Configurations
on Pages 15 and 16.
FoR VeRtICAl teRMINAtIoN
Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical
rise in an attic or second story, and allow for sufficient vent height above the roof line.
Note:
You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when
using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combina-
tion of 90° and 45° elbows up to a maximum of 70°.
For two-story applications, firestops are required at each floor level. If an offset is needed in the
attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. Refer
to
Installing Vent System in a Chase
below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its balance between the combustion air intake and
the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.
INStAllING A VeNt SySteM IN AN outSIDe CHASe
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a build-
ing. A chase is required for such venting.
W
ARNING
Never run the vent pipe down. this may
cause excessive temperatures which could
cause a fire.
N
ot
IC
e
When installing in a chase, you should insulate the chase as you would the
outside walls of your home. this is especially important in cold climates.
Insulation should be considered a combustible material. Maintain proper
clearances to all combustible materials.
N
ot
IC
e
treatment of firestops and construction of the chase may vary from
building type to building type. these instructions are not substitutes
for the requirements of local building codes. you must follow all local
building codes.