HDV Series Direct Vent Gas Fireplace
VeNtING INStAllAtIoN
ReAR WAll VeNt INStAllAtIoN (5"
x
8"
VeNtING oNly)
When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear wall
behind the appliance
•
The maximum horizontal distance between the rear
of the appliance and the termination is 0" (508 mm).
Figure 14
•
Only one 45° elbow is allowed in these installations.
DVR584-600
Rear vent no elbows
2/99 djt
0"
Maximum
DVR584
Figure 14 -
Rear Vent Application,
Maximum Horizontal Distance
1. Rigid vent pipes and fittings have special twist-lock
connections. Assemble the desired combination of pipe
and elbows to the appliance adaptor.
twist-lock Procedure:
The female ends of the pipes
and fittings have three locking lugs (indentations).
These lugs will slide straight into matching slots on
the male end of adjacent pipes and fittings. Push the
pipe sections together and twist one section clockwise
approximately one-quarter turn until the sections are
fully locked.
Figure 15
. Refer to venting and termination instructions for further
instructions.
Figure 15 -
Rigid Vent Pipe Connections
Note: Horizontal runs of
vent must be supported
every 3' (914 mm). use wall
straps for this purpose.
FP1953
rigid pipe
Female
Locking Lugs
Male Slots
FP1953
3. Locate and cut the vent opening in the wall. For com-
bustible walls first frame in opening.
Combustible Interior Walls:
Cut a 1
Z\x
"H x 10
Z\x
" W
hole through the interior wall.
Combustible exterior Walls:
Cut a 10
Z\x
"H x 10
Z\x
"W
square hole through the exterior wall frame.
Figure 16
Noncombustible Walls:
Hole opening should be 8
Z\x
"
(16 mm) in diameter.
4. The center of the hole should align with the center line
of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot.
Figure 16
VO584-100
Vent Opening
2/99 djt
Figure 16 -
Exterior Wall Framing Dimensions
10
Z\x
"
(67 mm)
10
Z\x
"
(67 mm)
Combustible Wall
Framing
VO584-100
8
Z\x
"
(16 mm)
Noncombustible Wall
5. Apply a bead of non-hardening mastic around the
outside edge of vent cap. Position the vent cap in the
center of hole on the exterior wall with the word “UP”
on the vent cap facing up. Insure proper clearance of
1" to combustibles is maintained. Attach the vent cap
with four wood screws supplied
.
Figure 17
Note:
Replace the wood screws with appropriate fasteners
for stucco, brick, concrete, or other types of siding.
For vinyl siding, stucco, or wood exterior use vinyl siding
standoffs between vent cap and exterior wall for Simpson
or Selkirk Terminations only. The vinyl siding standoff pre-
vents excessive heat from melting the vinyl siding material.
Note:
MHSC Terminations do not require standoff. Bolt
the vent cap to the standoff or wall. Apply non-hardening
mastic around outside edge of the standoff instead of the
vent cap assembly. Use wood screws provided to attach
the standoff.
Figure 18