1.0 OVERVIEW
The F2A1X Frequency to Analog Module converts frequency input into an
analog voltage (0 to 5 V dc) or current (4 to 20 m Adc) output. The output
is electrically isolated from the rest of the unit. The input signal may be
from an external sensor (measuring RPM for example) or any source of
digital signal not exceeding 12 volts.
The F2A1X may be factory preprogrammed or user programmed using an
optional USB programming cable (see Options and Accessories section) for
any full scale output and input scale factor to provide an output of mV or
mA out for a given input signal.
The device is powered from 12 to 24 V dc and consumes less than 100 mA
and can be operated freestanding or can be mounted to a panel using the
fixing wings on either end of the device. The F2A1X accepts input signals
from optical, infrared, laser or 3-wire proximity sensors, or direct TTL or
external ac inputs. User settings include sensor supply voltage, AC/DC
coupling and input termination.
When ordering the user needs to specify either a 4 to 20 mA current output
or 0 to 5 V dc voltage output and whether isolated outputs are required.
2.0 INSTALLATION
The F2A1X Frequency to Analog Module is housed in a mountable ABS
enclosure 3.2 x 1.6 x 1.2 inches [80 x 40 x 28 mm] excluding the mounting
wings. There are screw terminal connections on both ends of the unit.