Setting up your controller
XL-2
Manual
Page 18
Mold-Masters
®
Revision 1.1
6. Press to store the change. The bottom display starts flashing
again.
7. To exit from Program Menu, press .
Monitoring Temperature Limits
Your controller card looks at the actual temperature of each zone
and verifies that the zone is operating within specific limits.
Rather than fixed points of temperature, the Ot and Ut Limits are
set to degrees above the and below the set point. If these
temperatures are exceeded, the alarm relay on the XL-2 card
changes state to raise a disable injection interlock or alarm.
Setting Over Temperature Limit - Ot:
1. From the Temperature Display Screen, press and hold
button for at least 2 seconds until you get into Function Menu.
2. Use to scroll to “Prog”. Press to get into Program Menu.
3. The first parameter in Program Menu is Ot. You will see the
bottom display flashing.
4. Press to get access to change parameter setting. The bottom
display should stay.
5. Use or change to your desire setting.
6. Press to store the change. The bottom display should be
flashing again.
7.
Press to get back to Temperature Display Screen.
Setting Under Temperature Limit - Ut:
1. From the Temperature Display Screen, press and hold
button for at least 2 seconds until you get into Function Menu.
2. Use to scroll to “Prog”. Press to enter Program Menu.
3. Use to scroll to parameter “Ut”. You will see the bottom
display flashing.
4. Press to get access to change parameter setting. The
bottom display should stay.
5. Use or change to your desire setting.
6. Press to store the change. The bottom display starts
flashing again.
7. Press to get back to Temperature Display Screen.