26
Serial output:
TTL serial output for monitoring system (MODBUS-RTU) protocol
Data storing
: on the non-volatile memory (EEPROM).
Operating temperature:
0÷60 °C.
Storage temperature:
-30÷85 °C.
Relative humidity:
20÷85% (no condensing)
Measuring range:
-55÷50 °C
Resolution:
0,1 °C or 1 °F (selectable).
Accuracy of the controller at 25°C:
±0,3 °C ±1 digit
Standard value of the cycles
Cy1: for fast chilling and conservation of foods at positive temperature
CyS =
tEP
iS2 =
5°C
Pd3
= OFF
dbC =
yes
rS2
=+2°C
dbH
= yes
iS1 =
8°C
Pd2
= 3.0 h
HdS
= 2°C
rS1
= -10°C
iS3
= 5°C
Pd1
= 2.0 h
rS3
=+2°C
Cy2: for chilling and fast freezing of foods with holding
CyS =
tEP
iS2
= 5°C
Pd3
= 4.0 h
dbC =
YES
rS2
= +2°C
dbH = YES
iS1
= 8°C
Pd2
= 2.0 h
HdS =-21°C
rS1
= -10°C
iS3
=-18°C
Pd1
= 2.0 h
rS3
=-28°C
Cy3: direct fast freezing with holding
CyS =
tEP
iS2
=-18°C
Pd3
= 4
dbC =
yes
rS2
=-28°C
dbH = yes
iS1
= -18°C
Pd2
=OFF
HdS = -21°C
rS1
=-28°C
iS3
=-18°C
Pd1
= 4.0
rS3
=-28°C
Cy4: direct fast freezing without holding
CyS =
tEP
iS2
=-18°C
Pd3
= OFF
dbC =
yes
rS2
=-28°C
dbH
= no
iS1
=-18°C
Pd2
=OFF
HdS
= OFF
rS1
=-28°C
iS3
=-18°C
Pd1
= 4.0
rS3
=-28°C
Standard value of the parameters
Lab
Description
Values
Level
Set
Set point
2.0
- - -
Hy
differential
4.0
Pr1
AC
Anti-short cycle delay
4.0
Pr2
PAU
Time of stand by
20
Pr2
PFt
Maximum acceptable duration of power failure
15
Pr2
Con
Compressor ON time with faulty probe
15
Pr2
COF
Compressor OFF time with faulty probe
10
Pr2
rPO
Thermostat probe calibration
0.0
Pr2