© MOBATIME
29 / 40
800845.01
8
Testing mode, parameter reset
8.1
Synchronization test
The synchronization signal receive process can be displayed in special testing
mode. This can be useful for example when the problems with the DCF signal
receipt appear.
Display description during synchronization test mode:
Two digits on the left side show the current DCF bit number (goes up from 0 to
58). Third digit show the type of current DCF bit (0 or 1). The last digit shows the
number of successfully received DCF telegrams. The colon indicates that the
DCF bit is currently received. The dot behind the last digit signalizes
synchronized clock.
Entering the synchronization test mode:
Enter the clock menu and keep pushing simultaneously both buttons on the
clock PCB or the
DISP
button on the IR controller, until the display shows
C0:00
Use the
PB2
or
+
button on IR to set the value behind the colon to
03
Keep pushing simultaneously both clock PCB buttons or the
DISP
button on
IR, until the display shows synchronization information
8.2
Parameter reset
If necessary, the clock parameters can be set to factory defaults by the following
procedure.
Activating the parameter reset:
Enter the clock menu and keep pushing simultaneously both buttons on the
clock PCB or the
DISP
button on the IR controller, until the display shows
C0:00
Using the
PB2
or
+
button on IR set the value behind the colon to
04
Keep pushing simultaneously both clock PCB buttons or the DISP button on
IR, until the display shows FAC1 and clock makes reset