Chapter Three: Overview
Tuning the 640 Series Pressure Controller
37
Integral Term
The action of the Integral (I) term creates a valve drive signal that is proportional to the
magnitude and sign of the area under the error signal curve (error signal with respect to time).
Therefore, as time passes, the integral term acts to position the valve to reduce the error signal to
zero. An increase in the integration time increases the period of time over which the error signal
is generated, and the system response gets slower. Figure 16 shows the effects of the Integral
term.
Set Point Signal
Pressure Signal
Time
Pressure
Integral term set too low, (integration time
too long) system slow to reach set point
Pressure Signal
Set Point Signal
Time
Pressure
Integral term set too high, (integration time
too short) system overshoots the set point
Figure 16: Effects of the Integral Control
Adjusting the Integral Control
The Integral (I) term adjustment is located on the top of the 640 Series unit, as shown in
Figure 13, page 33. The control is a 10-position dial where the 0 setting has the longest
integration time; the 9 position setting has the shortest integration time. The initial setting is 0.
Note
To shorten the integration time, increase the I term setting.
Содержание 640A/641A
Страница 4: ...116669 P1 Rev C 12 99 MKS Type 640A 641A Pressure Controller...
Страница 9: ...Table of Contents vi...
Страница 11: ...List of Figures viii...
Страница 13: ...List of Tables x...
Страница 21: ...Customer Support Chapter One General Information 8 This page intentionally left blank...
Страница 45: ...Initial Configuration Chapter Two Installation 32 This page intentionally left blank...
Страница 69: ...Physical Specifications Appendix A Product Specifications 56 This page intentionally left blank...
Страница 85: ...Model Code Description Appendix D Model Code Explanation 72 This page intentionally left blank...