Chapter Two: Installation
The I/O Connector
13
The I/O Connector
The Type 640 Series controller has one 15-pin, male Type “D” connector that provides the
pressure output, set point input, and trip point output signals.
I/O Connector Pinout
Pin #
Assignment
1
Valve Test Point
2
Pressure Signal Output
3
Valve Close
4
Valve Open
5
Power Common
6
-15 V
7
+15 V
8
Set Point In
9
No Connection
10
Optional Input
11
Signal Common
12
Signal Common
13
Trip Point A Out
14
Trip Point B Out
15
Chassis Ground
Table 3: I/O Connector Pinout
Note
The “No Connection” pin assignment refers to a pin with no internal
connection.
Pressure Signal Output (Pin 2)
The 640 Series controller allows you to access the pressure signal from the transducer, correct it
in some way, and re-introduce it into pin 10 of the 640 Series controller to be used as the input
signal in closed-loop control. This function is useful if you need to correct for a zero offset.
Pin 2 accesses the pressure signal as it travels from the transducer to the control circuitry. Pin
10, re-introduces the signal into the 640 Series controller.
Содержание 640A/641A
Страница 4: ...116669 P1 Rev C 12 99 MKS Type 640A 641A Pressure Controller...
Страница 9: ...Table of Contents vi...
Страница 11: ...List of Figures viii...
Страница 13: ...List of Tables x...
Страница 21: ...Customer Support Chapter One General Information 8 This page intentionally left blank...
Страница 45: ...Initial Configuration Chapter Two Installation 32 This page intentionally left blank...
Страница 69: ...Physical Specifications Appendix A Product Specifications 56 This page intentionally left blank...
Страница 85: ...Model Code Description Appendix D Model Code Explanation 72 This page intentionally left blank...