Chapter Two: Installation
Initial Configuration
31
Initial Configuration
The 640 Series Pressure Controller is shipped from the factory with the configuration listed in
Table 8.
Initial Configuration
Feature
Setting
Options
Pressure Control
Downstream
Upstream
Set Point Input*
0 to 5 V
0 to 10 V
Pressure Output
0 to 5 V
0 to 10 V
Trip Point A
Setting
Action
100% F.S.
Trip high (TH)
1 to 100% F.S.
Trip low (TL)
Trip Point B
Setting
Action
1% F.S.
Trip low (TL)
1 to 100% F.S.
Trip high (TH)
P Term
Position 0
8 settings (0 through 7) on a 10 position dial
(8 repeats setting 0; and 9 repeats setting 1)
I Term
Position 0
10 settings, 0 through 9
* Input must match the pressure output signal range
Table 8: Initial Configuration