6
Design notes
The Mixergy cylinder is currently available in two basic variations:
• Mixergy Direct - Provides hot water heated by electricity and is
designed primarily for use with off peak electricity.
• Mixergy Indirect - Provides hot water either by electricity or an
internal primary coil which is designed for use with electric,
gas or oil fired boilers.
In addition, Mixergy cylinders can be fitted with the following op-
tions:
• External heat exchanger for use with electric, gas or oil fired
boilers and heat pump systems.
• Dual primary element for use with a PV diverter.
The unit should be handled with care in order to avoid damage. It
should be stored upright in a dry place.
Unvented hot water cylinders must not be used with
solid fuel boilers as the energy source.
All models are factory fitted / supplied with immer-
sion heaters that have built-in thermal cut-outs. Im-
mersion heaters without thermal cut-outs must not
be fitted.
All unvented installations must be fitted with a pres-
sure reducing valve (supplied) and P&T relief valve
(fitted). These must not be removed or used for any
other purposes than what they are designed for.
Содержание M0008
Страница 15: ...15 Installation electrical...
Страница 16: ...16 Installation electrical...
Страница 33: ...33 Service record Service date Serviced by Comments...
Страница 35: ......