background image

-

 0 

-

– 33 –

Insulation of connecting portion

1

Cover the connection portion of the refrigerant piping with the
pipe cover and seal them.
If neglecting to do so, moisture occurs on the piping and water
will drip out.

2

Finishing and fixing

a

Tie up the piping with wrapping tape, and shape it so that it conforms

to which the pipe is attached.

b

Fix them with clamps as right figure.

Vinyl tape

To cover the connecting portion with insula-
tion materials, cut upper portion and then seal
it with insulation materials.

Cover the exterior portion with cov-
ering tape and shape the piping so it
will match the contours of the route
that the piping to take. Also fix the
wiring and pipings to the wall with
clamps.

Insulation

Refrigerant piping
Electrical wiring
Covering tape
Drain hose

Tapping screw

 Additional refrigerant charge

Air purge

1

Tighten all flare nuts in the pipings both
indoor  and  outside  wall  so  as  not  to
cause leak.

2

Connect  service  valve,  charge  hose,
manifold valve and vacuum pump as is
illustrated below.

3

Open  manifold  valve  handle  Lo  to  its
full  width,  and  perform  vacuum  or
evacuation.
Continue the vacuum or evacuation op-
eration  for  15  minutes  or  more  and
check  to  see  that  the  vacuum  gauge
reads – 0.1 MPa (– 76 cmHg).

4

After  completing  vacuum  operation,
fully  open  service  valve  (Both  gas  and
liquid  sides)  with  hexagon  headed
wrench.

5

Detach the charge hoses.

6

Check for possible leakage of gas in the
connection parts of both indoor and out-
door.

(three-way valve)

Charge hose (Designed specifically for R410A)

Compound pressure gauge

Pressure gauge

Gauge manifold

(Designed specifically for R410A)

Handle Hi

Vacuum pump

Vacuum pump adapter

(Anti-reverse flow type)

(Designed specifically for R410A)

Charge hose

(Designed specifically for R410A)

Check joint 

-0.1MPa

(-76cmHg)

 Handle Lo

Operation valve

 Operation valve

(two-way valve)

Operation valve

cap

Operation valve

cap

Operation valve cap
tightening torque (N•m)

Check joint blind nut
tightening torque (N•m)

ø6.35  (1/4")
ø9.52  (3/8")

10~12

ø12.7  (1/2")

25~35

20~30

Operation valve size

(mm)

Securely tighten the operation valve cap and the check joint blind nut after adjustment.

¡

Since the system uses check joints differing in diameter from those found on the conventional models, a charge hose (for R22) presently in use is

not applicable.
Please use one designed specifically for R410A.

¡

Please use an anti-reverse flow type vacuum pump adapter so as to prevent vacuum pump oil from running back into the system.

Oil running back into an air-conditioning system may cause the refrigerant cycle to break down.

Model

SRK/C10YJV-S

SRK/C13YJV-S

Additional refrigerant

Less than 10m : Not required
More than 10m : 20g/m

Not required

How to relocate or dispose of the unit

In order to protect the environment, be sure to pump down (recovery of
refrigerant).

Pump down is the method of recovering refrigerant from the indoor unit
to the outdoor unit when the pipes are removed from the unit.

<How to pump down>

1

Connect charge hose to check joint.

2

Liquid side : Close the liquid valve with hexagon wrench key.
Gas side : Fully open the gas valve.
Carry  out  cooling  operation.  (If  indoor  temperature  is  low,  operate
forced cooling operation.)

3

After low pressure gauge become 0.01MPa, stop cooling operation and

close the gas valve.

¡

Forced cooling operation
Turn on a power supply again after a while after turn
off a power supply. Then press continually the ON/
OFF button 5 seconds or more.

Unit ON/OFF button

RMA012A032_Installation.p65

04/05/2010, 17:28

33

Содержание SRK10YJV-S

Страница 1: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONER Split system air cooled cooling only type SRK10YJV S 13YJV S Manual No 10 SRK T 103...

Страница 2: ...TECHNICAL MANUAL...

Страница 3: ...ler 5 Flap and louver control 24 4 Custom cord switching procedure 23 3 Auto restart function 2 Unit ON OFF button 23 22 8 Installation location setting 26 10 Outline of automatic operation 27 9 Outli...

Страница 4: ...nit inspection points 47 8 Phenomenon observed after shortcircuit wire breakage on sensor 45 9 Checking the indoor electrical equipment 45 How to read the model name Example SRK 10 Y Series code Inver...

Страница 5: ...reless Remote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Orange Safety devices Compressor overheat protection Overcurrent...

Страница 6: ...ote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Orange Safety devices Compressor overheat protection Overcurrent protectio...

Страница 7: ...et for wiring Drain hose Liquid piping F E C D B Symbol A 65 VP16 6 35 1 4 Flare Content 65 9 52 3 8 Flare Outlet for piping on both side G Note 1 The model name label is attached on the underside of...

Страница 8: ...s height 6 The model name label is attached on the lower right comer of the front panel L4 L3 L1 Intake Service space Intake Outlet Minimum installation space L2 L2 L3 L4 L1 100 100 250 Open Open 250...

Страница 9: ...3 Wireless remote controller Unit mm 60 17 3 150...

Страница 10: ...reen Y G Color Mark Heat exch sensor Fan motor Room temp sensor Flap motor Diode stack DS Fuse F Connector CNE CNU FM Terminal block T Description Item Varistor Va SM Louver motor LM1 2 ThI Th2 Yellow...

Страница 11: ...M 3 250V 15A Y G T1 T2 OR Y M t TH1TH2 TH3 EEV FMo CM t t t L TERMINAL N 1 3 2 BLOCK T TO INDOOR UNIT POWER WIRES SIGNAL WIRE POWER SOURCE 220V 50Hz Color RD Mark Orange OR Yellow Green Y G Black BK...

Страница 12: ...10 09 SRK DB 087D 5 PIPING SYSTEM Models SRK20ZJ S 25ZJ S Model SRK35ZJ S Humidity sensor HD 4 PIPING SYSTEM Model SRK10YJV S Model SRK13YJV S...

Страница 13: ...ing capacity in relation to temperatures Cooling 22 20 18 16 14 0 6 0 7 0 8 0 9 1 0 1 2 1 1 1 3 0 5 10 15 Applicable range Depends on installed situation 24 26 20 25 30 35 40 46 ISO T1 Standard Condit...

Страница 14: ...rection of cooling capacity in relation to one way length of refrigerant piping How to obtain the cooling capacity Piping length m Cooling 7 1 0 10 0 99 15 0 975 20 0 965 25 0 95 30 0 935 SRK13YJV S S...

Страница 15: ...d line and gas line until com pleted refrigerant piping work air tightness test and evacuation If the compressor is operated in state of opening operation valves before completed connection of refrige...

Страница 16: ...e remarkable decrease in performance corrosion and damage of components malfunction and fire Do not install the indoor unit in the locations listed below Be sure to install the indoor unit according t...

Страница 17: ...like so that the operation noise will cause no trouble A place where there is possibility of flammable gas leakage A place exposed to strong wind 5 Blowing out port and suction port on the back side o...

Страница 18: ...ice 100 102 5 585 102 5 133 5 450 206 5 202 450 138 44 5 43 2 39 3 200 65 15 Limitations for one way piping length and vertical height difference Model SRK10YJV S Item SRK13YJV S Total one way piping...

Страница 19: ...e Attach the lid f Close the air inlet panel 2 Shaping the pipe 3 Taping of the exterior Hold the bottom of the pipe and change its direction before stretching it and shaping it Tape only the portion...

Страница 20: ...rews 1 Removing Remove the 2 set screws Move the lower part of the panel forward and push upwards to remove Remove the 3 latches in the upper section 2 Fitting Do remove the air filter Cover the body...

Страница 21: ...Remove Do not turn Spanner for fixing the piping Torque wrench Specified torquing value Liquid side 6 35 14 18N m 1 4 1 8kgf m Gas side 9 52 34 42N m 3 4 4 2kgf m Gas side 12 7 49 62N m 4 9 6 2kgf m 1...

Страница 22: ...pump adapter Anti reverse flow type Designed specifically for R410A Charge hose Designed specifically for R410A Check joint 0 1MPa 76cmHg Handle Lo Operation valve Operation valve two way valve Operat...

Страница 23: ...Battery Cover Fixing to pillar or wall Conventionally operate the wireless remote control by holding in your hand Avoid installing it on a clay wall etc Screws CAUTION Do not use new and old batterie...

Страница 24: ...rate with lamp CLEAN indicator Indicates during CLEAN operation ON OFF TIMER indicator Indicates during ON OFF TIMER operation AIR FLOW indicator Shows selected flap and louver mode 3D AUTO indicator...

Страница 25: ...th boards If only one board is modified receiving and operation cannot be done a Modifying the indoor unit s printed circuit board Take out the printed circuit board from the control box and cut off j...

Страница 26: ...pprox 60 Angle of Flap from Horizontal Center installation Remote controller display Right end installation Left end installation Angle of Louver Left Approx 45 Left Approx 45 Left Approx 20 Left Appr...

Страница 27: ...izontal blowing Fixed Flap Louver Cooling Up down Swing Center Fixed Wide Fixed Flap Louver Cooling Horizontal blowing Fixed Operation mode Indoor temp Setting temp 2 C At cooling Air flow direction c...

Страница 28: ...ress the A desired loca Take the air conditioning unit s location into account and adjust the left right airflow Center 2 Press the AIRFLOW or more The installa 1 If the air c button to The installa 4...

Страница 29: ...perature and the outdoor air temperature determines the operation mode and then begins in the automatic operation Dehumidifying Cooling Indoor air temperature C Outdoor air temperature C b The unit ch...

Страница 30: ...the speed is reduced to 0 rps 3 Reset conditions When either of the following condition is satisfied a When the outdoor air temperature becomes 40 C or less b When the compressor command speed is 0rps...

Страница 31: ...n is continued with the lower limit speed forcibly h Indoor fan motor protection When the air conditioner is operating and the indoor fan motor is turned ON if the indoor fan motor has operated at 300...

Страница 32: ...pen 3 Troubleshooting procedure If the air conditioner does not run at all If the air conditioner does not run at all diagnose the trouble using the following troubleshooting procedure If the air cond...

Страница 33: ...ble and perform an operation check The air conditioning system is operating normally Replace the faulty component then perform an operation check Identify the faulty component by using the check proce...

Страница 34: ...poor connector connection Outdoor PCB is faulty 4 time flash Keeps flashing The inverter output current compressor motor current exceeds the set value during compressor start The air conditioner stop...

Страница 35: ...are recorded when trouble occurs so more detailed information can be checked These are the data which display the reason by a stop occurred when the air conditioning system performed protective stops...

Страница 36: ...remote controller information at the time the error code was displayed in the past Displays the outdoor air temperature sensor temperature at the time the error code was displayed in the past Display...

Страница 37: ...time the compressor started When it is judged that the power transistor was damaged at the time the compressor started When the curent is 1A or less the time the compressor started When there is a cu...

Страница 38: ...ed Rotor lock Rotor lock Protective control operation Indoor unit fan motor is abnormal Discharge pipe sensor is abnormal anomalous stop Indoor heat exchanger sensor is abnormal anomalous stop Outdoor...

Страница 39: ...f times in If no is displayed the error display shows that the trouble has occurred once Notes 3 Automatic Recovery Does not occur Automatic recovery occurs d Remote controller information tables 1 Op...

Страница 40: ...46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 29 19 9 9 19 29 39 49 59 69 79 89 99 No does not sound If no data are recorded e...

Страница 41: ...74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound If no data is recorded error code is normal the display for sensor becomes as shown below Sensor name Di...

Страница 42: ...Indoor heat exchanger sensor temperature on fourth previous occasion Remote control information on fourth previous occasion Outdoor air temperature sensor temperature on fourth previous occasion Outdo...

Страница 43: ...king sure the DC fan motor and indoor PCB are normal connect the connectors and confirm that the fan motor is turning If power is turned on while one or the other is broken down it could cause the oth...

Страница 44: ...ction of insufficient gas refrigerant Does compressor operation Is capacitor for compressor normal Replace compressor Replace heat exchanger sensor Insufficient gas Is refrigerant amount normal Is hea...

Страница 45: ...of signal transmission Wiring error including power cable defective indoor outdoor PCB Does error persist after power reset Are the lines connecting the indoor and outdoor units connected normally Is...

Страница 46: ...tion resistance 1 M or over Check coil wire resistance Model 10 13 1 703 U V V W U W or more at 20 C Is output voltage applied to all 3 phases of power transistor Inspect compressor Defective outdoor...

Страница 47: ...n Disconnected wire Humidity reading is 0 Operates in the Dry region Disconnected wire Humidity reading is 0 Operates in the Dry region Disconnected wire Humidity reading is 0 Operates in the Dry regi...

Страница 48: ...n the ON OFF button is pressed if trouble is detected after the voltages in the following figure are output for approximately 30 seconds it means that the indoor PCB is normal and the fan motor is bro...

Страница 49: ...ction of sensor characteristics on page 41 Inspection power transistor Remove the fasten terminal and test output voltage Inspection of electronic expansion valve See page 48 Inspection of outdoor fan...

Страница 50: ...detected diagnose which of the outdoor unit fan motor or outdoor PCB is defective Diagnose this only after confirming that the indoor unit is normal 1 Outdoor PCB output check 1 Turn off the power 2...

Страница 51: ...49...

Страница 52: ...50 PARTS LIST INDOOR UNIT SRK10YJV S SRK13YJV S OUTDOOR UNIT SRC10YJV S SRC13YJV S...

Страница 53: ...51 CRAE0229 2 14 9 8 14 14 10 10 12 12 24 11 21 17 22 13 4 5 1 31 28 30 35 35 6 3 3 4 16 22 25 21 7 27 26 32 34 33 29 18 20 15 22 19 23 PANEL FAN ASSY...

Страница 54: ...CONNECTING L 1 14 RKW935C200 COLLAR 6 15 RKX129A010 BRACKET MOTOR A 1 1 1 1 2 16 RKX129A011 BRACKET MOTOR B 1 1 1 1 2 17 RKX129A012 BRACKET MOTOR C 1 1 1 1 2 18 RKX144A001 LINK 1 1 1 1 2 19 RKX144A002...

Страница 55: ...53 CRAE0230 21 17 23 24 22 18 1 8 5 7 6 3 2 4 16 9 11 12 19 13 14 15 20 25 10 HEAT EXCH CONTROL...

Страница 56: ...58AD VARISTOR 1 1 1 1 2 Z 12 SSA564A132 FUSE CURRENT 1 1 1 2 4 F 3A 13 SSA551A163L SENSOR ASSY 1 1 1 2 4 INCL SENSOR ROOM TEMP HEAT EXCH 14 RKV504A500 HARNESS ASSY POWER 1 1 1 1 2 15 SSA561B702B BLOCK...

Страница 57: ...55 CRAE0229 2 14 9 8 14 14 10 10 12 12 24 11 21 17 22 13 4 5 1 31 28 30 35 35 6 3 3 4 16 22 25 21 7 27 26 32 34 33 29 18 20 15 22 19 23 PANEL FAN ASSY...

Страница 58: ...CONNECTING L 1 14 RKW935C200 COLLAR 6 15 RKX129A010 BRACKET MOTOR A 1 1 1 1 2 16 RKX129A011 BRACKET MOTOR B 1 1 1 1 2 17 RKX129A012 BRACKET MOTOR C 1 1 1 1 2 18 RKX144A001 LINK 1 1 1 1 2 19 RKX144A002...

Страница 59: ...57 CRAE0231 20 13 15 16 24 21 17 18 19 26 22 25 30 28 29 27 23 1 12 3 14 7 5 4 6 8 2 9 11 10 HEAT EXCH CONTROL...

Страница 60: ...5A500HF PWB ASSY 1 2 2 4 8 15 SSA555B058AD VARISTOR 1 1 1 1 2 Z 16 SSA564A132 FUSE CURRENT 1 1 1 2 4 F 3A 17 SSA551A163L SENSOR ASSY 1 1 1 2 4 INCL SENSOR ROOM TEMP HEAT EXCH 18 RKV504A500 HARNESS ASS...

Страница 61: ...59 CRBE0294 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY...

Страница 62: ...OUTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 8 SSA913A034F SCREW TAP 28 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A005 BRACKET ASSY 1 12 SSA512T09...

Страница 63: ...61 CRBE0291 18 19 22 20 23 24 CONTROL ASSY 21 27 28 21 25 1 21 26 9 3 5 12 13 10 14 7 8 6 11 2 16 4 17 15 GAS LIQ HEAT EXCH CONTROL...

Страница 64: ...L SOLENOID 1 FOR EEV 12 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 13 SSA914C013A NUT FLANGE 2 14 SSA941C346 CUSHION RUBBER 3 15 RSA932C004 GASKET COVER 1 16 RSA947K005 COVER TERMINAL 1 1 1 2 4 17 SSA914C...

Страница 65: ...63 CRBE0294 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY...

Страница 66: ...OUTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 8 SSA913A034F SCREW TAP 29 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A005 BRACKET ASSY 1 12 SSA512T09...

Страница 67: ...65 CRBE0292 18 19 22 20 23 24 CONTROL ASSY 21 27 28 21 25 1 21 26 9 3 5 12 13 10 14 7 8 6 11 2 16 4 17 15 GAS LIQ HEAT EXCH CONTROL...

Страница 68: ...L SOLENOID 1 FOR EEV 12 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 13 SSA914C013A NUT FLANGE 2 14 SSA941C346 CUSHION RUBBER 3 15 RSA932C004 GASKET COVER 1 16 RSA947K005 COVER TERMINAL 1 1 1 2 4 17 SSA914C...

Страница 69: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...

Отзывы: