background image

-

  

-

– 27 –

 CAUTION

Use the circuit breaker with sufficient breaking capacity.
If the breaker does not have sufficient breaking capacity, it can cause the unit

malfunction and fire.

Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause electric shocks.

Install isolator or disconnect switch on the power supply wiring in ac-

cordance with the local codes and regulations.

Be  sure  to  install  indoor  unit  properly  according  to  the  instruction

manual in order to run off the drainage smoothly.
Improper installation of indoor unit can cause dropping water into the room

and damaging personal property.

Install the drainage pipe to run off drainage securely according to the

installation manual.
Incorrect installation of the drainage pipe can cause dropping water into the

room and damaging personal property.

Be  sure  to  install  the  drainage  pipe  with  descending  slope  of  1/100  or

more, and not to make traps and air-bleedings.
Check if the drainage runs off securely during commissioning and ensure the

space for inspection and maintenance.

After  maintenance,  all  wiring,  wiring  ties  and  the  like,  should  be  re-

turned to their original state and wiring route, and the necessary clear-

ance from all metal parts should be secured.

Secure a space for installation, inspection and maintenance specified in

the manual.
Insufficient space can result in accident such as personal injury due to falling

from the installation place.

Take care when carrying the unit by hand.
If the unit weights more than 20kg, it must be carried by two or more per-

sons. Do not carry by the plastic straps, always use the carry handle when

carrying  the  unit  by  hand.  Use  gloves  to  minimize  the  risk  of  cuts  by  the

aluminum fins.

Dispose of any packing materials correctly.
Any  remaining  packing  materials  can  cause  personal  injury  as  it  contains

nails and wood. And to avoid danger of suffocation, be sure to keep the plas-

tic wrapper away from children and to dispose after tear it up.

For  installation  work,  be  careful  not  to  get  injured  with  the  heat  ex-

changer, piping flare portion or screws etc.

Be sure to insulate the refrigerant pipes so as not to condense the ambi-

ent air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture

damage on the ceiling, floor, furniture and any other valuables.

When perform the air conditioner operation (cooling or drying opera-

tion) in which ventilator is installed in the room. In this case, using the

air conditioner in parallel with the ventilator, there is the possibility that

drain water may backflow in accordance with the room lapse into the

negative pressure status. Therefore, set up the opening port such as in-

corporate the air into the room that may appropriate to ventilation (For

example; Open the door a little). In addition, just as above, so set up the

opening port if the room lapse into negative pressure status due to regis-

ter of the wind for the high rise apartment etc.

Do not install the unit in the locations listed below.

Locations where carbon fiber, metal powder or any powder is floating.

Locations where any substances that can affect the unit such as sulphide

gas, chloride gas, acid and alkaline can occur.

Vehicles and ships.

Locations where cosmetic or special sprays are often used.

Locations with direct exposure of oil mist and steam such as kitchen and

machine plant.

Locations where any machines which generate high frequency harmonics

are used.

Locations with salty atmospheres such as coastlines.

Locations with heavy snow (If installed, be sure to provide base flame and

snow hood mentioned in the manual).

Locations where the unit is exposed to chimney smoke.

Locations at high altitude (more than 1000m high).

Locations with ammonic atmospheres.

Locations where heat radiation from other heat source can affect the unit.

Locations without good air circulation.

Locations with any obstacles which can prevent inlet and outlet air of the

unit.

Locations where short circuit of air can occur (in case of multiple units

installation).

Locations where strong air blows against the air outlet of outdoor unit.

It can cause remarkable decrease in performance, corrosion and damage of

components, malfunction and fire.

Do not install the indoor unit in the locations listed below (Be sure to

install  the  indoor  unit  according  to  the  installation  manual  for  each

model because each indoor unit has each limitation).

Locations with any obstacles which can prevent inlet and outlet air of the

unit.

Locations where vibration can be amplified due to insufficient strength of

structure.

Locations where the infrared receiver is exposed to the direct sunlight or

the strong light beam (in case of the infrared specification unit).

Locations where an equipment affected by high harmonics is placed (TV

set or radio receiver is placed within 1m).

Locations where drainage cannot run off safely.

It can affect performance or function and etc.

Do not install the outdoor unit in the locations listed below.

Locations where discharged hot air or operating sound of the outdoor unit

can bother neighborhood.

Locations where outlet air of the outdoor unit blows directly to plants.

Locations where vibration can be amplified and transmitted due to insuffi-

cient strength of structure.

Locations where vibration and operation sound generated by the outdoor

unit can affect seriously (on the wall or at the place near bed room).

Locations where an equipment affected by high harmonics is placed (TV

set or radio receiver is placed within 1m).

Locations where drainage cannot run off safely.

It can affect surrounding environment and cause a claim.

Do not install the unit near the location where leakage of combustible

gases can occur.
If leaked gases accumulate around the unit, it can cause fire.

Do not install the unit where corrosive gas (such as sulfurous acid gas

etc.) or combustible gas (such as thinner and petroleum gases) can accu-

mulate or collect, or where volatile combustible substances are handled.
Corrosive  gas  can  cause  corrosion  of  heat  exchanger,  breakage  of  plastic

parts and etc. And combustible gas can cause fire.

Do not use the indoor unit at the place where water splashes may occur

such as in laundries.
Since the indoor unit is not waterproof, it can cause electric shocks and fire.

Do not install nor use the system close to the equipment that generates

electromagnetic fields or high frequency harmonics.
Equipment  such  as  inverters,  standby  generators,  medical  high  frequency

equipments and telecommunication equipments can affect the system, and

cause  malfunctions  and  breakdowns.  The  system  can  also  affect  medical

equipment  and  telecommunication  equipment,  and  obstruct  its  function  or

cause jamming.

Do not place any variables which will be damaged by getting wet under

the indoor unit.
When the relative humidity is higher than 80% or drainage pipe is clogged,

condensation or drainage water can drop and it can cause the damage of valu-

ables.

Do not install the remote control at the direct sunlight.
It can cause malfunction or deformation of the remote control.

Do not use the unit for special purposes such as storing foods, cooling

precision instruments and preservation of animals, plants or art.
It can cause the damage of the items.

Do not install the outdoor unit in a location where insects and small ani-

mals can inhabit.
Insects and small animals can enter the electric parts and cause damage or

fire. Instruct the user to keep the surroundings clean.

Do not use the base flame for outdoor unit which is corroded or dam-

aged due to long periods of operation.
Using an old and damage base flame can cause the unit falling down and

cause personal injury.

Do not use any materials other than a fuse with the correct rating in the

location where fuses are to be used.
Connecting the circuit with copper wire or other metal thread can cause unit

failure and fire.

Do not touch any buttons with wet hands.
It can cause electric shocks.

Do not touch any refrigerant pipes with your hands when the system is

in operation.
During operation the refrigerant pipes become extremely hot or extremely

cold depending the operating condition, and it can cause burn injury or frost

injury.

Do not touch the suction or aluminum fin on the outdoor unit.
This may cause injury.

Do not put anything on the outdoor unit and operating unit.
This may cause damage the objects or injury due to falling to the object.

RMA012A032_Installation.p65

04/05/2010, 17:28

27

Содержание SRK10YJV-S

Страница 1: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONER Split system air cooled cooling only type SRK10YJV S 13YJV S Manual No 10 SRK T 103...

Страница 2: ...TECHNICAL MANUAL...

Страница 3: ...ler 5 Flap and louver control 24 4 Custom cord switching procedure 23 3 Auto restart function 2 Unit ON OFF button 23 22 8 Installation location setting 26 10 Outline of automatic operation 27 9 Outli...

Страница 4: ...nit inspection points 47 8 Phenomenon observed after shortcircuit wire breakage on sensor 45 9 Checking the indoor electrical equipment 45 How to read the model name Example SRK 10 Y Series code Inver...

Страница 5: ...reless Remote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Orange Safety devices Compressor overheat protection Overcurrent...

Страница 6: ...ote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Orange Safety devices Compressor overheat protection Overcurrent protectio...

Страница 7: ...et for wiring Drain hose Liquid piping F E C D B Symbol A 65 VP16 6 35 1 4 Flare Content 65 9 52 3 8 Flare Outlet for piping on both side G Note 1 The model name label is attached on the underside of...

Страница 8: ...s height 6 The model name label is attached on the lower right comer of the front panel L4 L3 L1 Intake Service space Intake Outlet Minimum installation space L2 L2 L3 L4 L1 100 100 250 Open Open 250...

Страница 9: ...3 Wireless remote controller Unit mm 60 17 3 150...

Страница 10: ...reen Y G Color Mark Heat exch sensor Fan motor Room temp sensor Flap motor Diode stack DS Fuse F Connector CNE CNU FM Terminal block T Description Item Varistor Va SM Louver motor LM1 2 ThI Th2 Yellow...

Страница 11: ...M 3 250V 15A Y G T1 T2 OR Y M t TH1TH2 TH3 EEV FMo CM t t t L TERMINAL N 1 3 2 BLOCK T TO INDOOR UNIT POWER WIRES SIGNAL WIRE POWER SOURCE 220V 50Hz Color RD Mark Orange OR Yellow Green Y G Black BK...

Страница 12: ...10 09 SRK DB 087D 5 PIPING SYSTEM Models SRK20ZJ S 25ZJ S Model SRK35ZJ S Humidity sensor HD 4 PIPING SYSTEM Model SRK10YJV S Model SRK13YJV S...

Страница 13: ...ing capacity in relation to temperatures Cooling 22 20 18 16 14 0 6 0 7 0 8 0 9 1 0 1 2 1 1 1 3 0 5 10 15 Applicable range Depends on installed situation 24 26 20 25 30 35 40 46 ISO T1 Standard Condit...

Страница 14: ...rection of cooling capacity in relation to one way length of refrigerant piping How to obtain the cooling capacity Piping length m Cooling 7 1 0 10 0 99 15 0 975 20 0 965 25 0 95 30 0 935 SRK13YJV S S...

Страница 15: ...d line and gas line until com pleted refrigerant piping work air tightness test and evacuation If the compressor is operated in state of opening operation valves before completed connection of refrige...

Страница 16: ...e remarkable decrease in performance corrosion and damage of components malfunction and fire Do not install the indoor unit in the locations listed below Be sure to install the indoor unit according t...

Страница 17: ...like so that the operation noise will cause no trouble A place where there is possibility of flammable gas leakage A place exposed to strong wind 5 Blowing out port and suction port on the back side o...

Страница 18: ...ice 100 102 5 585 102 5 133 5 450 206 5 202 450 138 44 5 43 2 39 3 200 65 15 Limitations for one way piping length and vertical height difference Model SRK10YJV S Item SRK13YJV S Total one way piping...

Страница 19: ...e Attach the lid f Close the air inlet panel 2 Shaping the pipe 3 Taping of the exterior Hold the bottom of the pipe and change its direction before stretching it and shaping it Tape only the portion...

Страница 20: ...rews 1 Removing Remove the 2 set screws Move the lower part of the panel forward and push upwards to remove Remove the 3 latches in the upper section 2 Fitting Do remove the air filter Cover the body...

Страница 21: ...Remove Do not turn Spanner for fixing the piping Torque wrench Specified torquing value Liquid side 6 35 14 18N m 1 4 1 8kgf m Gas side 9 52 34 42N m 3 4 4 2kgf m Gas side 12 7 49 62N m 4 9 6 2kgf m 1...

Страница 22: ...pump adapter Anti reverse flow type Designed specifically for R410A Charge hose Designed specifically for R410A Check joint 0 1MPa 76cmHg Handle Lo Operation valve Operation valve two way valve Operat...

Страница 23: ...Battery Cover Fixing to pillar or wall Conventionally operate the wireless remote control by holding in your hand Avoid installing it on a clay wall etc Screws CAUTION Do not use new and old batterie...

Страница 24: ...rate with lamp CLEAN indicator Indicates during CLEAN operation ON OFF TIMER indicator Indicates during ON OFF TIMER operation AIR FLOW indicator Shows selected flap and louver mode 3D AUTO indicator...

Страница 25: ...th boards If only one board is modified receiving and operation cannot be done a Modifying the indoor unit s printed circuit board Take out the printed circuit board from the control box and cut off j...

Страница 26: ...pprox 60 Angle of Flap from Horizontal Center installation Remote controller display Right end installation Left end installation Angle of Louver Left Approx 45 Left Approx 45 Left Approx 20 Left Appr...

Страница 27: ...izontal blowing Fixed Flap Louver Cooling Up down Swing Center Fixed Wide Fixed Flap Louver Cooling Horizontal blowing Fixed Operation mode Indoor temp Setting temp 2 C At cooling Air flow direction c...

Страница 28: ...ress the A desired loca Take the air conditioning unit s location into account and adjust the left right airflow Center 2 Press the AIRFLOW or more The installa 1 If the air c button to The installa 4...

Страница 29: ...perature and the outdoor air temperature determines the operation mode and then begins in the automatic operation Dehumidifying Cooling Indoor air temperature C Outdoor air temperature C b The unit ch...

Страница 30: ...the speed is reduced to 0 rps 3 Reset conditions When either of the following condition is satisfied a When the outdoor air temperature becomes 40 C or less b When the compressor command speed is 0rps...

Страница 31: ...n is continued with the lower limit speed forcibly h Indoor fan motor protection When the air conditioner is operating and the indoor fan motor is turned ON if the indoor fan motor has operated at 300...

Страница 32: ...pen 3 Troubleshooting procedure If the air conditioner does not run at all If the air conditioner does not run at all diagnose the trouble using the following troubleshooting procedure If the air cond...

Страница 33: ...ble and perform an operation check The air conditioning system is operating normally Replace the faulty component then perform an operation check Identify the faulty component by using the check proce...

Страница 34: ...poor connector connection Outdoor PCB is faulty 4 time flash Keeps flashing The inverter output current compressor motor current exceeds the set value during compressor start The air conditioner stop...

Страница 35: ...are recorded when trouble occurs so more detailed information can be checked These are the data which display the reason by a stop occurred when the air conditioning system performed protective stops...

Страница 36: ...remote controller information at the time the error code was displayed in the past Displays the outdoor air temperature sensor temperature at the time the error code was displayed in the past Display...

Страница 37: ...time the compressor started When it is judged that the power transistor was damaged at the time the compressor started When the curent is 1A or less the time the compressor started When there is a cu...

Страница 38: ...ed Rotor lock Rotor lock Protective control operation Indoor unit fan motor is abnormal Discharge pipe sensor is abnormal anomalous stop Indoor heat exchanger sensor is abnormal anomalous stop Outdoor...

Страница 39: ...f times in If no is displayed the error display shows that the trouble has occurred once Notes 3 Automatic Recovery Does not occur Automatic recovery occurs d Remote controller information tables 1 Op...

Страница 40: ...46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 29 19 9 9 19 29 39 49 59 69 79 89 99 No does not sound If no data are recorded e...

Страница 41: ...74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound If no data is recorded error code is normal the display for sensor becomes as shown below Sensor name Di...

Страница 42: ...Indoor heat exchanger sensor temperature on fourth previous occasion Remote control information on fourth previous occasion Outdoor air temperature sensor temperature on fourth previous occasion Outdo...

Страница 43: ...king sure the DC fan motor and indoor PCB are normal connect the connectors and confirm that the fan motor is turning If power is turned on while one or the other is broken down it could cause the oth...

Страница 44: ...ction of insufficient gas refrigerant Does compressor operation Is capacitor for compressor normal Replace compressor Replace heat exchanger sensor Insufficient gas Is refrigerant amount normal Is hea...

Страница 45: ...of signal transmission Wiring error including power cable defective indoor outdoor PCB Does error persist after power reset Are the lines connecting the indoor and outdoor units connected normally Is...

Страница 46: ...tion resistance 1 M or over Check coil wire resistance Model 10 13 1 703 U V V W U W or more at 20 C Is output voltage applied to all 3 phases of power transistor Inspect compressor Defective outdoor...

Страница 47: ...n Disconnected wire Humidity reading is 0 Operates in the Dry region Disconnected wire Humidity reading is 0 Operates in the Dry region Disconnected wire Humidity reading is 0 Operates in the Dry regi...

Страница 48: ...n the ON OFF button is pressed if trouble is detected after the voltages in the following figure are output for approximately 30 seconds it means that the indoor PCB is normal and the fan motor is bro...

Страница 49: ...ction of sensor characteristics on page 41 Inspection power transistor Remove the fasten terminal and test output voltage Inspection of electronic expansion valve See page 48 Inspection of outdoor fan...

Страница 50: ...detected diagnose which of the outdoor unit fan motor or outdoor PCB is defective Diagnose this only after confirming that the indoor unit is normal 1 Outdoor PCB output check 1 Turn off the power 2...

Страница 51: ...49...

Страница 52: ...50 PARTS LIST INDOOR UNIT SRK10YJV S SRK13YJV S OUTDOOR UNIT SRC10YJV S SRC13YJV S...

Страница 53: ...51 CRAE0229 2 14 9 8 14 14 10 10 12 12 24 11 21 17 22 13 4 5 1 31 28 30 35 35 6 3 3 4 16 22 25 21 7 27 26 32 34 33 29 18 20 15 22 19 23 PANEL FAN ASSY...

Страница 54: ...CONNECTING L 1 14 RKW935C200 COLLAR 6 15 RKX129A010 BRACKET MOTOR A 1 1 1 1 2 16 RKX129A011 BRACKET MOTOR B 1 1 1 1 2 17 RKX129A012 BRACKET MOTOR C 1 1 1 1 2 18 RKX144A001 LINK 1 1 1 1 2 19 RKX144A002...

Страница 55: ...53 CRAE0230 21 17 23 24 22 18 1 8 5 7 6 3 2 4 16 9 11 12 19 13 14 15 20 25 10 HEAT EXCH CONTROL...

Страница 56: ...58AD VARISTOR 1 1 1 1 2 Z 12 SSA564A132 FUSE CURRENT 1 1 1 2 4 F 3A 13 SSA551A163L SENSOR ASSY 1 1 1 2 4 INCL SENSOR ROOM TEMP HEAT EXCH 14 RKV504A500 HARNESS ASSY POWER 1 1 1 1 2 15 SSA561B702B BLOCK...

Страница 57: ...55 CRAE0229 2 14 9 8 14 14 10 10 12 12 24 11 21 17 22 13 4 5 1 31 28 30 35 35 6 3 3 4 16 22 25 21 7 27 26 32 34 33 29 18 20 15 22 19 23 PANEL FAN ASSY...

Страница 58: ...CONNECTING L 1 14 RKW935C200 COLLAR 6 15 RKX129A010 BRACKET MOTOR A 1 1 1 1 2 16 RKX129A011 BRACKET MOTOR B 1 1 1 1 2 17 RKX129A012 BRACKET MOTOR C 1 1 1 1 2 18 RKX144A001 LINK 1 1 1 1 2 19 RKX144A002...

Страница 59: ...57 CRAE0231 20 13 15 16 24 21 17 18 19 26 22 25 30 28 29 27 23 1 12 3 14 7 5 4 6 8 2 9 11 10 HEAT EXCH CONTROL...

Страница 60: ...5A500HF PWB ASSY 1 2 2 4 8 15 SSA555B058AD VARISTOR 1 1 1 1 2 Z 16 SSA564A132 FUSE CURRENT 1 1 1 2 4 F 3A 17 SSA551A163L SENSOR ASSY 1 1 1 2 4 INCL SENSOR ROOM TEMP HEAT EXCH 18 RKV504A500 HARNESS ASS...

Страница 61: ...59 CRBE0294 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY...

Страница 62: ...OUTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 8 SSA913A034F SCREW TAP 28 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A005 BRACKET ASSY 1 12 SSA512T09...

Страница 63: ...61 CRBE0291 18 19 22 20 23 24 CONTROL ASSY 21 27 28 21 25 1 21 26 9 3 5 12 13 10 14 7 8 6 11 2 16 4 17 15 GAS LIQ HEAT EXCH CONTROL...

Страница 64: ...L SOLENOID 1 FOR EEV 12 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 13 SSA914C013A NUT FLANGE 2 14 SSA941C346 CUSHION RUBBER 3 15 RSA932C004 GASKET COVER 1 16 RSA947K005 COVER TERMINAL 1 1 1 2 4 17 SSA914C...

Страница 65: ...63 CRBE0294 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY...

Страница 66: ...OUTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 8 SSA913A034F SCREW TAP 29 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A005 BRACKET ASSY 1 12 SSA512T09...

Страница 67: ...65 CRBE0292 18 19 22 20 23 24 CONTROL ASSY 21 27 28 21 25 1 21 26 9 3 5 12 13 10 14 7 8 6 11 2 16 4 17 15 GAS LIQ HEAT EXCH CONTROL...

Страница 68: ...L SOLENOID 1 FOR EEV 12 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 13 SSA914C013A NUT FLANGE 2 14 SSA941C346 CUSHION RUBBER 3 15 RSA932C004 GASKET COVER 1 16 RSA947K005 COVER TERMINAL 1 1 1 2 4 17 SSA914C...

Страница 69: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...

Отзывы: