background image

-

  

-

6. APPLICATION DATA

– 26 –

Safety precautions

When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping

length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.

We recommend you to read this “SAFETY PRECAUTIONS” carefully before the installation work in order to gain full advantage of the func-

tions of the unit and to avoid malfunction due to mishandling.

The precautions described below are divided into 

WARNING

and

CAUTION

. The matters with possibilities leading to serious conse-

quences such as death or serious personal injury due to erroneous handling are listed in the

WARNING

and the matters with possibilities

leading to personal injury or damage of the unit due to erroneous handling including probability leading to serious consequences in some cases
are listed in 

CAUTION

 . These are very important precautions for safety. Be sure to observe all of them without fail.

Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the

maintenance methods of this equipment to the user according to the owner’s manual.

Keep the installation manual together with owner’s manual at a place where any user can read at any time. Moreover if necessary, ask to hand

them to a new user.

For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then perform

the installation works.

Please pay attention not to fall down the tools, etc. when installing the unit at the high position.

If unusual noise can be heard during operation, consult the dealer.

Symbols which appear frequently in the text have the following meaning:

Observe instructions
with great care

Strictly prohibited

Provide proper earthing

WARNING

Installation must be carried out by the qualified installer.
If you install the system by yourself, it may cause serious trouble such as

water leaks, electric shocks, fire and personal injury, as a result of a system

malfunction.

Install the system in full accordance with the instruction manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric

shocks and fire.

Be sure to use only for household and residence.
If this appliance is installed in inferior environment such as machine shop

and etc., it can cause malfunction.

Use the original accessories and the specified components for installation.
If parts other than those prescribed by us are used, It may cause water leaks,

electric shocks, fire and personal injury.

Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall and cause material

damage and personal injury.

Ensure the unit is stable when installed, so that it can withstand earth-

quakes and strong winds.
Unsuitable installation locations can cause the unit to fall and cause material

damage and personal injury.

Ventilate the working area well in the event of refrigerant leakage dur-

ing installation.
If  the  refrigerant  comes  into  contact  with  naked  flames,  poisonous  gas  is

produced.

When installing in small rooms, take prevention measures not to exceed

the density limit of refrigerant in the event of leakage.
Consult the expert about prevention measures. If the density of refrigerant

exceeds the limit in the event of leakage, lack of oxygen can occur, which

can cause serious accidents.

After completed installation, check that no refrigerant leaks from the system.
If  refrigerant  leaks  into  the  room  and  comes  into  contact  with  an  oven  or

other hot surface, poisonous gas is produced.

Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and seri-

ous accidents due to burst of the refrigerant circuit.

Tighten the flare nut by torque wrench with specified method.
If the flare nut were tightened with excess torque, this may cause burst and

refrigerant leakage after a long period.

Do not open the operation valves for liquid line and gas line until com-

pleted refrigerant piping work, air tightness test and evacuation.
If  the  compressor  is  operated  in  state  of  opening  operation  valves  before

completed connection of refrigerant piping work, air can be sucked into re-

frigerant circuit, which can cause bust or personal injury due to anomalously

high pressure in the refrigerant.

Do not put the drainage pipe directly into drainage channels where poi-

sonous gases such as sulphide gas can occur.
Poisonous gases will flow into the room through drainage pipe and seriously

affect the user’s health and safety.

Ensure that no air enters in the refrigerant circuit when the unit is in-

stalled and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit

becomes too high, which can cause burst and personal injury.

Do not processing, splice the power cord, or share a socket with other

power plugs.
This may cause fire or electric shock due to defecting contact, defecting in-

sulation and over-current etc.

The electrical installation must be carried out by the qualified electri-

cian in accordance with “the norm for electrical work” and “national

wiring regulation”, and the system must be connected to the dedicated

circuit.
Power supply with insufficient capacity and incorrect function done by im-

proper work can cause electric shocks and fire.

Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or incor-

rect function of equipment.

Be  sure  to  use  the  cables  conformed  to  safety  standard  and  cable

ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production or

fire.

This appliance must be connected to main power supply by means of a

circuit breaker or switch (fuse:16A) with a contact separation of at least

3mm.

When  plugging  this  appliance,  a  plug  conforming  to  the  norm

IEC60884-1 must be used.

Use  the  prescribed  cables  for  electrical  connection,  tighten  the  cables

securely  in  terminal  block  and  relieve  the  cables  correctly  to  prevent

overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat production

or fire.

Arrange  the  wiring  in  the  control  box  so  that  it  cannot  be  pushed  up

further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.

Be sure to fix up the service panels.
Incorrect fixing can cause electric shocks or fire due to intrusion of dust or

water.

Be sure to switch off the power supply in the event of installation, inspec-

tion or servicing.
If  the  power  supply  is  not  shut  off,  there  is  a  risk  of  electric  shocks,  unit

failure or personal injury due to the unexpected start of fan.

Stop  the  compressor  before  disconnecting  refrigerant  pipes  in  case  of

pump down operation.
If disconnecting refrigerant pipes in state of opening operation valves before

compressor stopping, air can be sucked, which can cause burst or personal

injury due to anomalously high pressure in the refrigerant circuit

Only use prescribed optional parts. The installation must be carried out

by the qualified installer.
If  you  install  the  system  by  yourself,  it  can  cause  serious  trouble  such  as

water leaks, electric shocks, fire.

Do not bundling, winding or processing for the power cord. Or, do not

deforming the power plug due to tread it.
This may cause fire or heating.

Do not vent R410A into the atmosphere : R410A is a fluorinated green-

house gas, covered by the Kyoto Protocol with Global Warming Poten-

tial (GWP)=1975.

Do not run the unit with removed panels or protections.
Touching rotating equipments, hot surfaces or high voltage parts can cause

personal injury due to entrapment, burn or electric shocks.

Do not perform any change of protective device itself or its setup condition.
The forced operation by short-circuiting protective device of pressure switch

and temperature controller or the use of non specified component can cause

fire or burst.

Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such

as electric shocks due to short-circuiting.

RMA012A032_Installation.p65

04/05/2010, 17:28

26

Содержание SRK10YJV-S

Страница 1: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONER Split system air cooled cooling only type SRK10YJV S 13YJV S Manual No 10 SRK T 103...

Страница 2: ...TECHNICAL MANUAL...

Страница 3: ...ler 5 Flap and louver control 24 4 Custom cord switching procedure 23 3 Auto restart function 2 Unit ON OFF button 23 22 8 Installation location setting 26 10 Outline of automatic operation 27 9 Outli...

Страница 4: ...nit inspection points 47 8 Phenomenon observed after shortcircuit wire breakage on sensor 45 9 Checking the indoor electrical equipment 45 How to read the model name Example SRK 10 Y Series code Inver...

Страница 5: ...reless Remote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Orange Safety devices Compressor overheat protection Overcurrent...

Страница 6: ...ote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Orange Safety devices Compressor overheat protection Overcurrent protectio...

Страница 7: ...et for wiring Drain hose Liquid piping F E C D B Symbol A 65 VP16 6 35 1 4 Flare Content 65 9 52 3 8 Flare Outlet for piping on both side G Note 1 The model name label is attached on the underside of...

Страница 8: ...s height 6 The model name label is attached on the lower right comer of the front panel L4 L3 L1 Intake Service space Intake Outlet Minimum installation space L2 L2 L3 L4 L1 100 100 250 Open Open 250...

Страница 9: ...3 Wireless remote controller Unit mm 60 17 3 150...

Страница 10: ...reen Y G Color Mark Heat exch sensor Fan motor Room temp sensor Flap motor Diode stack DS Fuse F Connector CNE CNU FM Terminal block T Description Item Varistor Va SM Louver motor LM1 2 ThI Th2 Yellow...

Страница 11: ...M 3 250V 15A Y G T1 T2 OR Y M t TH1TH2 TH3 EEV FMo CM t t t L TERMINAL N 1 3 2 BLOCK T TO INDOOR UNIT POWER WIRES SIGNAL WIRE POWER SOURCE 220V 50Hz Color RD Mark Orange OR Yellow Green Y G Black BK...

Страница 12: ...10 09 SRK DB 087D 5 PIPING SYSTEM Models SRK20ZJ S 25ZJ S Model SRK35ZJ S Humidity sensor HD 4 PIPING SYSTEM Model SRK10YJV S Model SRK13YJV S...

Страница 13: ...ing capacity in relation to temperatures Cooling 22 20 18 16 14 0 6 0 7 0 8 0 9 1 0 1 2 1 1 1 3 0 5 10 15 Applicable range Depends on installed situation 24 26 20 25 30 35 40 46 ISO T1 Standard Condit...

Страница 14: ...rection of cooling capacity in relation to one way length of refrigerant piping How to obtain the cooling capacity Piping length m Cooling 7 1 0 10 0 99 15 0 975 20 0 965 25 0 95 30 0 935 SRK13YJV S S...

Страница 15: ...d line and gas line until com pleted refrigerant piping work air tightness test and evacuation If the compressor is operated in state of opening operation valves before completed connection of refrige...

Страница 16: ...e remarkable decrease in performance corrosion and damage of components malfunction and fire Do not install the indoor unit in the locations listed below Be sure to install the indoor unit according t...

Страница 17: ...like so that the operation noise will cause no trouble A place where there is possibility of flammable gas leakage A place exposed to strong wind 5 Blowing out port and suction port on the back side o...

Страница 18: ...ice 100 102 5 585 102 5 133 5 450 206 5 202 450 138 44 5 43 2 39 3 200 65 15 Limitations for one way piping length and vertical height difference Model SRK10YJV S Item SRK13YJV S Total one way piping...

Страница 19: ...e Attach the lid f Close the air inlet panel 2 Shaping the pipe 3 Taping of the exterior Hold the bottom of the pipe and change its direction before stretching it and shaping it Tape only the portion...

Страница 20: ...rews 1 Removing Remove the 2 set screws Move the lower part of the panel forward and push upwards to remove Remove the 3 latches in the upper section 2 Fitting Do remove the air filter Cover the body...

Страница 21: ...Remove Do not turn Spanner for fixing the piping Torque wrench Specified torquing value Liquid side 6 35 14 18N m 1 4 1 8kgf m Gas side 9 52 34 42N m 3 4 4 2kgf m Gas side 12 7 49 62N m 4 9 6 2kgf m 1...

Страница 22: ...pump adapter Anti reverse flow type Designed specifically for R410A Charge hose Designed specifically for R410A Check joint 0 1MPa 76cmHg Handle Lo Operation valve Operation valve two way valve Operat...

Страница 23: ...Battery Cover Fixing to pillar or wall Conventionally operate the wireless remote control by holding in your hand Avoid installing it on a clay wall etc Screws CAUTION Do not use new and old batterie...

Страница 24: ...rate with lamp CLEAN indicator Indicates during CLEAN operation ON OFF TIMER indicator Indicates during ON OFF TIMER operation AIR FLOW indicator Shows selected flap and louver mode 3D AUTO indicator...

Страница 25: ...th boards If only one board is modified receiving and operation cannot be done a Modifying the indoor unit s printed circuit board Take out the printed circuit board from the control box and cut off j...

Страница 26: ...pprox 60 Angle of Flap from Horizontal Center installation Remote controller display Right end installation Left end installation Angle of Louver Left Approx 45 Left Approx 45 Left Approx 20 Left Appr...

Страница 27: ...izontal blowing Fixed Flap Louver Cooling Up down Swing Center Fixed Wide Fixed Flap Louver Cooling Horizontal blowing Fixed Operation mode Indoor temp Setting temp 2 C At cooling Air flow direction c...

Страница 28: ...ress the A desired loca Take the air conditioning unit s location into account and adjust the left right airflow Center 2 Press the AIRFLOW or more The installa 1 If the air c button to The installa 4...

Страница 29: ...perature and the outdoor air temperature determines the operation mode and then begins in the automatic operation Dehumidifying Cooling Indoor air temperature C Outdoor air temperature C b The unit ch...

Страница 30: ...the speed is reduced to 0 rps 3 Reset conditions When either of the following condition is satisfied a When the outdoor air temperature becomes 40 C or less b When the compressor command speed is 0rps...

Страница 31: ...n is continued with the lower limit speed forcibly h Indoor fan motor protection When the air conditioner is operating and the indoor fan motor is turned ON if the indoor fan motor has operated at 300...

Страница 32: ...pen 3 Troubleshooting procedure If the air conditioner does not run at all If the air conditioner does not run at all diagnose the trouble using the following troubleshooting procedure If the air cond...

Страница 33: ...ble and perform an operation check The air conditioning system is operating normally Replace the faulty component then perform an operation check Identify the faulty component by using the check proce...

Страница 34: ...poor connector connection Outdoor PCB is faulty 4 time flash Keeps flashing The inverter output current compressor motor current exceeds the set value during compressor start The air conditioner stop...

Страница 35: ...are recorded when trouble occurs so more detailed information can be checked These are the data which display the reason by a stop occurred when the air conditioning system performed protective stops...

Страница 36: ...remote controller information at the time the error code was displayed in the past Displays the outdoor air temperature sensor temperature at the time the error code was displayed in the past Display...

Страница 37: ...time the compressor started When it is judged that the power transistor was damaged at the time the compressor started When the curent is 1A or less the time the compressor started When there is a cu...

Страница 38: ...ed Rotor lock Rotor lock Protective control operation Indoor unit fan motor is abnormal Discharge pipe sensor is abnormal anomalous stop Indoor heat exchanger sensor is abnormal anomalous stop Outdoor...

Страница 39: ...f times in If no is displayed the error display shows that the trouble has occurred once Notes 3 Automatic Recovery Does not occur Automatic recovery occurs d Remote controller information tables 1 Op...

Страница 40: ...46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 29 19 9 9 19 29 39 49 59 69 79 89 99 No does not sound If no data are recorded e...

Страница 41: ...74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound If no data is recorded error code is normal the display for sensor becomes as shown below Sensor name Di...

Страница 42: ...Indoor heat exchanger sensor temperature on fourth previous occasion Remote control information on fourth previous occasion Outdoor air temperature sensor temperature on fourth previous occasion Outdo...

Страница 43: ...king sure the DC fan motor and indoor PCB are normal connect the connectors and confirm that the fan motor is turning If power is turned on while one or the other is broken down it could cause the oth...

Страница 44: ...ction of insufficient gas refrigerant Does compressor operation Is capacitor for compressor normal Replace compressor Replace heat exchanger sensor Insufficient gas Is refrigerant amount normal Is hea...

Страница 45: ...of signal transmission Wiring error including power cable defective indoor outdoor PCB Does error persist after power reset Are the lines connecting the indoor and outdoor units connected normally Is...

Страница 46: ...tion resistance 1 M or over Check coil wire resistance Model 10 13 1 703 U V V W U W or more at 20 C Is output voltage applied to all 3 phases of power transistor Inspect compressor Defective outdoor...

Страница 47: ...n Disconnected wire Humidity reading is 0 Operates in the Dry region Disconnected wire Humidity reading is 0 Operates in the Dry region Disconnected wire Humidity reading is 0 Operates in the Dry regi...

Страница 48: ...n the ON OFF button is pressed if trouble is detected after the voltages in the following figure are output for approximately 30 seconds it means that the indoor PCB is normal and the fan motor is bro...

Страница 49: ...ction of sensor characteristics on page 41 Inspection power transistor Remove the fasten terminal and test output voltage Inspection of electronic expansion valve See page 48 Inspection of outdoor fan...

Страница 50: ...detected diagnose which of the outdoor unit fan motor or outdoor PCB is defective Diagnose this only after confirming that the indoor unit is normal 1 Outdoor PCB output check 1 Turn off the power 2...

Страница 51: ...49...

Страница 52: ...50 PARTS LIST INDOOR UNIT SRK10YJV S SRK13YJV S OUTDOOR UNIT SRC10YJV S SRC13YJV S...

Страница 53: ...51 CRAE0229 2 14 9 8 14 14 10 10 12 12 24 11 21 17 22 13 4 5 1 31 28 30 35 35 6 3 3 4 16 22 25 21 7 27 26 32 34 33 29 18 20 15 22 19 23 PANEL FAN ASSY...

Страница 54: ...CONNECTING L 1 14 RKW935C200 COLLAR 6 15 RKX129A010 BRACKET MOTOR A 1 1 1 1 2 16 RKX129A011 BRACKET MOTOR B 1 1 1 1 2 17 RKX129A012 BRACKET MOTOR C 1 1 1 1 2 18 RKX144A001 LINK 1 1 1 1 2 19 RKX144A002...

Страница 55: ...53 CRAE0230 21 17 23 24 22 18 1 8 5 7 6 3 2 4 16 9 11 12 19 13 14 15 20 25 10 HEAT EXCH CONTROL...

Страница 56: ...58AD VARISTOR 1 1 1 1 2 Z 12 SSA564A132 FUSE CURRENT 1 1 1 2 4 F 3A 13 SSA551A163L SENSOR ASSY 1 1 1 2 4 INCL SENSOR ROOM TEMP HEAT EXCH 14 RKV504A500 HARNESS ASSY POWER 1 1 1 1 2 15 SSA561B702B BLOCK...

Страница 57: ...55 CRAE0229 2 14 9 8 14 14 10 10 12 12 24 11 21 17 22 13 4 5 1 31 28 30 35 35 6 3 3 4 16 22 25 21 7 27 26 32 34 33 29 18 20 15 22 19 23 PANEL FAN ASSY...

Страница 58: ...CONNECTING L 1 14 RKW935C200 COLLAR 6 15 RKX129A010 BRACKET MOTOR A 1 1 1 1 2 16 RKX129A011 BRACKET MOTOR B 1 1 1 1 2 17 RKX129A012 BRACKET MOTOR C 1 1 1 1 2 18 RKX144A001 LINK 1 1 1 1 2 19 RKX144A002...

Страница 59: ...57 CRAE0231 20 13 15 16 24 21 17 18 19 26 22 25 30 28 29 27 23 1 12 3 14 7 5 4 6 8 2 9 11 10 HEAT EXCH CONTROL...

Страница 60: ...5A500HF PWB ASSY 1 2 2 4 8 15 SSA555B058AD VARISTOR 1 1 1 1 2 Z 16 SSA564A132 FUSE CURRENT 1 1 1 2 4 F 3A 17 SSA551A163L SENSOR ASSY 1 1 1 2 4 INCL SENSOR ROOM TEMP HEAT EXCH 18 RKV504A500 HARNESS ASS...

Страница 61: ...59 CRBE0294 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY...

Страница 62: ...OUTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 8 SSA913A034F SCREW TAP 28 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A005 BRACKET ASSY 1 12 SSA512T09...

Страница 63: ...61 CRBE0291 18 19 22 20 23 24 CONTROL ASSY 21 27 28 21 25 1 21 26 9 3 5 12 13 10 14 7 8 6 11 2 16 4 17 15 GAS LIQ HEAT EXCH CONTROL...

Страница 64: ...L SOLENOID 1 FOR EEV 12 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 13 SSA914C013A NUT FLANGE 2 14 SSA941C346 CUSHION RUBBER 3 15 RSA932C004 GASKET COVER 1 16 RSA947K005 COVER TERMINAL 1 1 1 2 4 17 SSA914C...

Страница 65: ...63 CRBE0294 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY...

Страница 66: ...OUTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 8 SSA913A034F SCREW TAP 29 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A005 BRACKET ASSY 1 12 SSA512T09...

Страница 67: ...65 CRBE0292 18 19 22 20 23 24 CONTROL ASSY 21 27 28 21 25 1 21 26 9 3 5 12 13 10 14 7 8 6 11 2 16 4 17 15 GAS LIQ HEAT EXCH CONTROL...

Страница 68: ...L SOLENOID 1 FOR EEV 12 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 13 SSA914C013A NUT FLANGE 2 14 SSA941C346 CUSHION RUBBER 3 15 RSA932C004 GASKET COVER 1 16 RSA947K005 COVER TERMINAL 1 1 1 2 4 17 SSA914C...

Страница 69: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...

Отзывы: