7 - 6 7 - 6
MELSEC-Q
7 PARAMETER SETTING
7.2 Basic Parameters
7.2.1 Basic parameters details
The basic parameters are classified into the following three types.
(1) TCP/UDP/IP setting
Address
Parameter Name
Setting Range
Initial Value
0000
H
(0)
TCP ULP timer value
Set time = set value 500ms
2 to 2400
60
0001
H
(1)
TCP zero window timer value
Set time = set value 500ms
2 to 2400
20
0002
H
(2)
TCP resend timer value
Set time = set value 500ms
2 to 2400
20
0003
H
(3)
TCP end timer value
Set time = set value 500ms
2 to 2400
40
0004
H
(4)
IP reassembly timer value
Set time = set value 500ms
1 to 2399
10
0005
H
(5)
TCP/UDP/IP
monitoring
timer
Split reception monitoring timer value
Set time = set value 500ms
2 to 2400
60
0006
H
(6)
KeepAlive
0: Not used
1: Used
1
0007
H
(7)
KeepAlive start timer value
Set time = set value 500ms
1 to 32767
1200
0008
H
(8)
KeepAlive interval timer value
Set time = set value 500ms
1 to 32767
20
0009
H
(9)
KeepAlive
KeepAlive resend count
1 to 10
3
000A
H
(10)
Router relay function
0: Not used
1: Used
0
000B
H
to 000C
H
(11 to 12)
Subnet mask pattern
C0000000
H
to
FFFFFFFC
H
FFFFFF00
H
000D
H
to 000E
H
(13 to 14)
Default router IP address
Refer to Section
7.2.2 (3) (c)
00000000
H
000F
H
(15)
Number of routers set
0 to 8
0
0010
H
to 0011
H
(16 to 17)
Subnet address
Refer to Section
7.2.2 (3) (e)
00000000
H
0012
H
to 0013
H
(18 to 19)
Router information 1
Router IP address
Refer to Section
7.2.2 (3) (f)
00000000
H
0014
H
to 002F
H
(20 to 47)
Routing
information
Router information 2 to 8
(Same as router information 1)