(1) Intelligent function module switch setting
Set the intelligent function module switches by clicking Switch setting on <<I/O
assignment>> of GX Developer.
For the program example, set intelligent function module switches as described
below.
Intelligent Function
Module Switch
Setting Details
Set Value
Switch 1
No need to set (initial value (online))
Switch 2
1) Basic parameter starting method
Start with the user-set parameters (b0: 1)
2) MODBUS
R
device assignment parameter starting method
Start with the user-set parameters (b1: 1)
3) Online change enable/disable setting
Online change enabled (b2: 1)
4) Send frame specification
Data are sent in Ethernet (V2.0)-compliant frame (b3: 0)
0007
H
( 1)
( 2)
( 3)
Switch 3
Set the (upper half) of the IP address
C001
H
Switch 4
Set the (lower half) of the IP address
0001
H
1: Set 0006
H
to start with the default basic parameters.
2: Set 0005
H
to start with the default MODBUS
R
device assignment parameters.
3: Set 0004
H
to start with the default basic and MODBUS
R
device assignment parameters.