4 - 8 4 - 8
MELSEC-Q
4 MODBUS
R
STANDARD FUNCTIONS
4.3.3 Read holding registers (FC: 03)
Reads the values of one or more holding registers.
Number of accessible devices with one message
1 to 125 points
(1) Request message format (Master Slave)
Head holding register number
Data
Read points
(H)
(L)
(H)
(L)
Function code
Function code
(0000
H
to FFFF
H
)
(03
H
)
(0001
H
to 007D
H
)
(2) Response message format (Slave Master)
(When completed normally)
Data
(H)
Function code
Function code
Device data
1
Device data
n
(Number of read bytes n 2)
*1:
(L)
(H)
(L)
Number of
read bytes
n 2*1
(03
H
)
For example, when n = 4, the number of
read bytes is 4 2 = 8 bytes.
(When completed with an error)
Data
Function code
Function code
(83
H
)
Exception
code*
2: When completed with an error, the exception code and error code are stored
into the buffer memory.
Refer to Section 11.3 for the storage location, confirmation method and more
details.
Содержание QJ71MT91
Страница 1: ......
Страница 2: ......
Страница 278: ...App 1 App 1 MELSEC Q APPENDICES APPENDICES Appendix 1 External Dimensions Unit mm in 27 4 1 08 90 3 54 98 3 86 APP ...
Страница 291: ......
Страница 292: ......