9 - 15 9 - 15
MELSEC-Q
9 PROGRAMMING
(b) Automatic communication parameters
Setting Item
Buffer Memory Address
Set Value
Target station IP address
0200
H
to 0201
H
(512 to 513)
C0010002
H
(192.1.0.2)
Module ID
0202
H
(514)
255
Repeat interval timer value
0203
H
(515)
1200(120s)
Response monitoring timer value
0204
H
(516)
60(30s)
Type specification of the target
MODBUS
R
device
0205
H
(517)
0100
H
(Read coils)
Head buffer memory
address
0206
H
(518)
1100
H
Target MODBUS
R
device head number
0207
H
(519)
15000
Automatic
communication
parameter 1
Read setting
Access points
0208
H
(520)
1024
Target station IP address
020C
H
to 020D
H
(524 to 525)
C0010002
H
(192.1.0.2)
Module ID
020E
H
(526)
255
Repeat interval timer value
020F
H
(527)
10(100ms)
Response monitoring timer value
0210
H
(528)
60(30s)
Type specification of the target
MODBUS
R
device
0211
H
(529)
0005
H
(Write holding registers)
Head buffer memory
address
0215
H
(533)
3A00
H
Target MODBUS
R
device head number
0216
H
(534)
0
Automatic
communication
parameter 2
Write setting
Access points
0217
H
(535)
100
(c) MODBUS
®
device assignment parameters
Setting Item
Buffer Memory Address
Set Value
Device code
0900
H
(2304)
009D
H
(Y: Output)
Head device number
0901
H
(2305)
0100
H
Head coil number
0902
H
(2306)
0 (000001)
Coil assignment 1
Assignment points
0903
H
(2307)
512 (points)
Device code
0980
H
(2432)
00A8
H
(D: Data register)
Head device number
0981
H
(2433)
3500
Head input register number
0982
H
(2434)
3499 (303500)
Input register
assignment 1
Assignment points
0983
H
(2435)
5500 (points)
Device code
09C0
H
(2496)
F000
H
(User free area)
Head device number
09C1
H
(2497)
5500
H
Head holding register number
09C2
H
(2498)
0 (400001)
Holding register
assignment 1
Assignment points
09C3
H
(2499)
1024 (points)